Callisto 5PX G2 Service Manual
Checked
:
Rev:
Approved
:
Confidential
Page 51 of 60
This specification is the property of Eaton Corp. and shall not be reproduced or copied or used as the basis for manufacture or sale of apparatus without permission
5.4
LCD Fault and Alarm messages
5.4.1 Fault/ alarm definitions
Rule1:
An alarm is displayed to warn the user about a special event, temporary defect or a load
incident.
It should not make the user call the Eaton service: no red led, no continuous buzzer sound.
The alarm message is displayed on status screen top row.
If the defect or incident cause disappears, then the alarm disappears.
A fault is displayed to warn the user about UPS failure or UPS mode change due to external
incident (Mains, load, temperature).
Fault display is: red led, continuous buzzer sound, fault message box.
Rule2:
When a defect has the possibility to be an alarm or a fault (example: overload, temperature),
then as long as the defect does not transfer to a permanent bypass mode or a stop: it is an
alarm/ otherwise it is a fault.