Mounting- and Operating Instruction CEAG DualGuard-S
40071860347 January 2020 www.ceag.de
43 DualGuard-S 20C6
Technical description
Field
Dimensions (W x H x D):
2000 x 800 x 600 mm
Colour:
RAL 7035
Weight:
216 kg
Assembly:
Ground
Degree of protection:
IP21, optional IP31, on request IP54
Protection class:
I
Ambient temperature:
-5°C to +35°C
Degree of pollution:
2
Electromagnetic compatibility:
Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains):
UN = 400/230 V AC
Rated current (Mains):
IN = 63 A
Rated voltage (Battery):
216 V DC
Rated current (Battery):
IN =63 A
Rated Frequency:
50 / 60 Hz
Overvoltage category:
Mains: III / Battery: II
Max. connected load:
At +35°C < 13,6 KW
Maximum numbers of modules:
Controller ACU DG / HMI:
1
PSU:
1-2
BCM.1:
1
SKU.1.1 CG-S:
1x6A
0-18
2x3A
0-18
4x1,5A
0-16
Luminaire circuits:
68
Charger CM 1,7A
0-2
Charger CM 3,4A
0-2
Terminals:
Luminaire circuits
4 mm² Rigid/4 mm² flexible
BCM.1
4 mm² Rigid/4 mm² flexible
ACU DG
2,5mm² Rigid/ 1,5mm² flexible
Battery feed
16 mm² Rigid/16 mm² flexible
Battery distribution
35 mm² Rigid/35 mm² flexible
Mains feed
16 mm² Rigid/16 mm² flexible
Mains distribution board
35 mm² Rigid/35 mm² flexible
Order number accesories:
Cupboard base 100mm
40071362284
Cupboard base 200mm
40071362285
IP 31 Retrofit kit
40071362297
Door hinge left
40071362306
Special development
40037079790