129
Mounting- and Operating Instruction CEAG DualGuard-S
40071860347 January 2020 www.ceag.de
52 DualGuard-S US SOU1
52 DualGuard-S US SOU1
The DualGuard-S US SOU1 sub-station in accordance with
EN 50171 supplies 230V / 216V AC/DC safety and escape
sign luminaires and is particularly suitable for installation
in fire compartments in buildings with a large number of
fire compartments. Thus, the decentralized design of the
system can contribute to reducing the costs for function
maintenance cabling. The automatic test device and indivi-
dual luminaire monitoring with individual status and name
indication per luminaire in conjunction with system-related
ECG / LED supply module including monitoring module
without additional data line reports and proclaims the ope-
rating states.
Consisting of:
Fire protection wall distributor with cable entry from above
and a SOU CG-S 2x4A circuit changeover.
Technical description
Field
Dimensions (W x H x D):
458x295x129 mm
Colour:
RAL 7032
Weight:
7,5 kg
Assembly:
Recommended for wall mounting: 4xM8 (min.
2xM8)
Force [N]: 1037
Mounting stability [N]: 525
Degree of protection:
IP65
Protection class:
I
Ambient temperature:
-5°C to +35°C
Degree of pollution:
2
Electromagnetic compatibility:
Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains):
UN = 230 V AC
A1
Rated current (Mains):
IN = 8 A
Rated voltage (Battery):
216 V DC
A2
Rated current (Battery):
IN =8 A
Rated Frequency:
50 / 60 Hz
Overvoltage category:
Mains: III / Battery: II
Max. connected load:
At +35°C < 1,7 KW
Maximum numbers of modules:
SOU CG-S 2x4A
1
B
Luminaire circuits:
2
A3
Terminals:
Luminaire circuits
4 mm² Rigid/flexible
A3
Battery feed
16 mm² Rigid/flexible
A2
Battery through-wiring
16 mm² Rigid/flexible
A2
Mains feed
16 mm² Rigid/flexible
A1
Mains through-wiring
16 mm² Rigid/flexible
A1
1 2 3 4
A
B
C