69
Mounting- and Operating Instruction CEAG DualGuard-S
40071860347 January 2020 www.ceag.de
31 CG V.1 Relay Module
31 CG V.1 Relay Module
The CGV.1 relay module is suitable for snap mounting on
the DualGuard-S module subrack and enables the connec-
tion of the DualGuard-S to a central control station (FÜB).
The most important system statuses are reported via
potential-free signalling contacts. Two input channels are
available for remote checking of the DualGuard-S central
battery system. A function test can be triggered via the
„FT“ input channel and an duration test (battery test) via
the „BT“ input channel. Eight LEDs indicate the system
status.
Switching capacity of the contacts: 24V/0,5A AC/DC
24V Function inputs
With a pulse of at least 20 ms/24 V the desired function
can be activated.
If a function or duration test is to be triggered again, the
function-duration test must be reset via a pulse.
Function test ON => 24V DC ≥ 20ms
Function test OFF => 24V DC ≥ 20ms
Battery duration test ON => 24V DC ≥ 20ms
Battery duration test OFF => 24V DC ≥ 20ms
Ordering details
Type
Description
Order No.
CG V.1
Relay module for subrack Mounting
40071361630
Function
Contact
11/12
Contact
21/22
Contact
31/32
Contact
41/42
Contact
51/52
Not ready for operation
ON
-
-
-
-
Disfunction Prior. 1
-
ON
-
-
-
Disfunction Prior. 2
-
-
ON
-
-
Disfunction Prior. 3
-
-
-
ON
-
Emergency mode
-
-
-
-
ON