80
Mounting- and Operating Instruction CEAG DualGuard-S
40071860347 January 2020 www.ceag.de
38 Connection distributor Mains
38 Connection distributor Mains
The mains power supply of the DualGuard-S 28 or
DualGuard-S 20 is provided via a modular mains connection
distributor. The distributor contains a size 00C switch-dis-
connector with a maximum connection cross-section of 50
mm2 and enables the connection of up to 6 substations to
modular size D02-E18 outgoing distribution boxes and the
associated terminals for the neutral and earth conductors.
In the case of outgoing feeders to powerful substations,
the same outgoing network distributors can also be used
in three phases (then connection of max. 2 substations).
The components are simply plugged on from the front and
securely contacted.
Ordering details
Type
Description
Order No.
Outgoing distribution module Mains
for busbar mounting
Incl. 3 pieces screw caps E18 and 3 pieces D02-
fuse links 25A
40071347160
Busbar cover profile
Cover profile in module width for clip mounting to
the bottom tray profile
40071347192
Name:
Data:
Pos.
Assembly:
On busbar
Degree of protection:
IP20
Protection class:
I
Ambient temperature:
55°C
Rated voltage (Mains):
UN = 400/230 V AC
Rated current (Mains):
IN = 63 A
Rated Frequency:
50 or 60 Hz
Maximum number of outgoing distributors
modules
6
Module
50 mm² Rigid/flexible
Terminals Connection cross-sections
Mains feed:
16 mm² Rigid/flexible
Terminals Connection cross-sections
Mains Distribuiton:
III for Mains