83
Mounting- and Operating Instruction CEAG DualGuard-S
40071860347 January 2020 www.ceag.de
40 DualGuard-S LAD 100
Technical description
Field
Dimensions (W x H x D):
2070 x 800 x 405 mm
Colour:
RAL 7035
Weight:
170 kg
Assembly:
Only set up on non-combustible ground (e.g. con-
crete).
Degree of protection:
IP21, optional IP31, on request IP54
Protection class:
I
Ambient temperature:
-5°C to +35°C
Degree of pollution:
2
Electromagnetic compatibility:
Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains):
UN = 400/230 V AC
Rated current (Mains):
IN = 100 A
Rated voltage (Battery):
216 V DC
Rated current (Battery):
IN =100 A
Rated Frequency:
50 or 60 Hz
Overvoltage category:
Mains: III / Battery: II
Max. Wärmeverlustleistung:
At +35°C < 21,6 KW
Maximum numbers of modules:
Controller ACU DG / HMI:
1
E1
PSU:
1-2
E1
BCM.1:
1
E2
SKU.1.1 CG-S:
E4
1x6A
0-4
2x3A
0-4
4x1,5A
0-4
Luminaire circuits:
16
D4
Charger CM 1,7A
1-2
E3
Charger CM 3,4A
0-8
F1-4
Terminals:
Luminaire circuits:
4 mm² Rigid / 4 mm² flexible
D4
BCM.1:
4 mm² Rigid / 4 mm² flexible
D4
ACU DG
2,5mm² Rigid / 1,5mm² flexible
D4
Battery feed:
50 mm² Rigid / 50 mm² flexible
B4
Battery distribution:
16 mm² Rigid / 16 mm² flexible
A4
Mains feed:
50 mm² Rigid / 50 mm² flexible
B1
Mains distribution board:
16 mm² Rigid / 16 mm² flexible
A1
Order number accesories:
Cupboard base 100mm
40071362282
Cupboard base 200mm
40071362283
Door hinge left
40071362301
Special locking profile half cylinder
40037079790
IP 31 Retrofit kit
40071362296