INSTALLATION AND OPERATION MANUAL
25-16327-B November 2020 www.eaton.com
Section 2: Commissioning
Isolate zone/address
User can define between zones or addresses to be isolated on activation of the
device . The isolate list button enables the user to enter upto 8 unique zones or
addresses . If non-latching has been enabled, Isolated devices can be un-isolated
as the triggered device returns to normal operation . (a call point keyswitch is an
example for this application) .
Device outputs
Delay configuration
The output of a device when triggered can be delayed - based on a user defined
value in minutes .
This programming option is enabled when a value other than zero is entered inside
the ‘Delay’ window .
MCP Override
This option is a manual intervention override, when enabled (check in box) the delay
can be overridden from any call point on the loop when triggered .
Daynight
See coincidence detection below .