Champ® MLLA M2 Series Linear Emergency LED
Luminaire Fittings for Hazardous Locations
Installation & Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
IF 1946
IF 1946 • 09/22 Copyright © 2022, Eaton’s Crouse-Hinds Division Page 1
APPLICATION
CHAMP Linear Emergency LED luminaire are suitable for use in the following
hazardous (classified) locations as defined by the National Electrical Code
(NEC®):
The assembled luminaire shall be installed in accordance with the National
Electric Code NFPA70, and American Bureau of Shipping.
NEC
•
Class I, Division 2, Groups A, B, C, D
•
Class I, Zone 2
•
Class II, Division 1, Groups E, F, G
•
Class III
•
Wet location, IP66/67, Type 4X
These luminaire housings shall be used with UL listed Crouse-Hinds hazard-
ous locations luminaire fittings namely LED Light Engine Cat Nos. MLLA*2 or
MLLA*4 series ending with M2 and Mounting means Cat Nos. M2-FLUSH-
MT-KIT, M2-CEILING-SWIVEL-KIT, M2-CEILING-WALL-KIT, M2-PM-KIT-1.25,
M2-PM-KIT-1.5, M2-PM-KIT-2.0, (refer to label provided inside the driver housing
for permissible fitting details).
UL Standards:
•
UL844 Hazardous (Classified)
•
UL1598 Luminaires, UL1598A Marine
• UL8750
• UL924
CSA Standard:
•
CSA C22.2 No. 250
•
CSA C22.2 No. No.137
•
CSA C22.2 No. No.141
Refer to the luminaire fitting nameplate for specific classification information,
maximum ambient temperature suitability, and corresponding operating
temperature (T-code).
The assembled linear LED luminaire is designed for use indoors and outdoors
in marine and wet locations, where moisture, dirt, corrosion, vibration and
rough usage may be present.
INPUT VOLTAGE:
•
UNV1: 120-277 VAC 50/60 Hz
1. Read carefully before installing and wiring luminaire and retain for future
reference.
2. Ensure area to be free of hazardous atmospheres before and during
installation and maintenance.
3. Do not use accessory equipment not recommended by manufacturer
may cause an unsafe condition.
4. Use only replacement parts from Eaton’s Crouse Hinds division.
5. To avoid the risk of fire, explosion or electric shock, this product should
be installed, inspected and maintained by a qualified electrician only, in
accordance with all applicable electrical codes.
6. Do not use this equipment for other than intended use.
7. Replace entire battery unit and LED driver when necessary. Contact the
manufacturer for information on service.
8. Do not attempt to service battery.
9. See product label for minimum supply wire temperature rating.
10. Battery requires 24hrs to fully charge. Allow 24 hours charging time
before depending on the battery to operate at full capacity.
11. The emergency battery requires a minimum charge time of one (1) hour
before testing the circuit, 24 hours is required for a full charge.
12. Equipment should be mounted in locations and at heights where it will
not readily be subjected to tampering by unauthorized personnel.
Max.
mounting height: 25.2 feet)
13. The emergency luminaire is intended to be installed with CG-256 (issued
by the American Bureau of Shipping and Coast Guard.
14. This product must be installed in accordance with the applicable installa-
tion code by a person familiar with the construction and operation of the
product and the hazards involved.
IMPORTANT SAFEGUARDS - READ AND FOLLOW ALL SAFETY INSTRUCTIONS
STORAGE INSTRUCTIONS
1.
EM luminaire must be stored in an ambient temperature range of 0°C
to 40°C.
2.
Battery should be charged and discharged within 6 months. At a
minimum, the battery should be recharged within this time.
WARNING
To avoid electric shock:
Be certain electrical power is OFF before and during installation and
maintenance.
Luminaire must be supplied by a wiring system with an equipment
grounding conductor in accordance to the NEC and CEC for the specific
Hazardous Locations involved.
To avoid burning hands:
Make sure lens and housing are cool when performing maintenance.
!
WARNING
To avoid explosion:
Make sure the supply voltage is the same as the luminaire voltage.
Do not install where the marked operating temperatures exceed the
ignition temperature of the hazardous atmosphere.
Do not operate in ambient temperatures above those indicated on the
luminaire nameplate.
Use proper supply wiring as specified on the luminaire nameplate.
All gasket seals must be clean and undamaged.
Before opening, electrical power to the luminaire must be turned off.
Keep tightly closed when in operation.
To reduce the risk of ignition due to electrostatic discharge, avoid contact
with the luminaire while explosive atmosphere is present. Clean only with
damp cloth.
!