S ECTION II - GENERAL DES CRIPTION
2.0 GENERAL
Type CM52 network protector is a special air
circuit breaker equipped with a relay that
operates in response to voltage across the
protector or current through the protector. This
relay caus es the protector to close or to open as
required by the conditions between the network
and the feeder trans formers. Control power is
taken directly from the system and therefore no
separate power source is required.
CM52 units are available as standard, for
216Y/125 volts, 480Y/277 volts at 60 Hertz,
with other voltages as well as 50 Hertz units
available upon request.
CAUTION
Type CM52 Netw ork Protectors are
protectiv e dev ices. As such, they are
maximum current rated devices.
Therefore, they should not under any
circumstances be applied outside of their
ratings , w hich could cause the
equipment to fail, resulting in severe
personal inj ury, death, or property
damage.
Fig. 3
NPL Fuse Housing (external fuses)
The standard submersible enclosure is equipped
with type NPL fuses in extern ally mounted fuse
housing located on top of the n etwork body. The
CM52 is also available with internal fuses.
The normal power flow is in at the throat from
the trans fo rmer, down to th e trans former side
disconnect device on the lev ering-out unit, up
through the unit to the network side disconnect
device, out the top o f th e en closure into the fuse
housings, through the fuse to the supplied
mounting terminal.
Fig. 3A
(Internal fuses)