background image

SCADA Terminal block connection procedures

SCADA terminal block connection can be completed via 

side-entry or front-entry connection. The maximum wire size 

to be used is #14. The minimum wire size to be used is #26. 

To connect the SCADA terminal block, use the screwdriver 

provided in the DC Motor Operator Control cabinet in 

conjunction with the following instructions (See Figure 9):
1.  Insert the screwdriver into the operating slot. 
2.  Insert stripped wire. Hold the clamping spring open 

with the screwdriver so that the conductor can be 

inserted into the clamping unit.

3.  Withdraw the screwdriver. The conductor will 

automatically be clamped.

Figure 8 .  SCADA terminal block connection procedures

DC Motor actuator

The DC Motor Operator Control is designed for operation 

with the DC Motor Operator. The DC Motor actuates to 

open or close when supplied with 24 Vdc via the control 

(See Figure 10).

Figure 9 .  DC Motor actuator - connected

941196KM

The DC motor actuator can be manually disconnected by 

removing the cotter pin which connects the motor to the 

yellow handle (See Figure 11).

Translator Tube

Figure 10 .  DC Motor actuator - disconnected

otee:

N

The actuator and limit switches are adjusted 

for proper operation prior to shipment. Moving 

the translator tube manually or electrically while 

disconnected from the switchgear will necessitate 

re-adjustment of the assembly.

Testing procedures

 WARNING

This equipment is not intended to protect human 

life . Follow all locally approved procedures and safety 

practices when installing or operating this equipment . 

Failure to comply can result in death, severe personal 

injury and equipment damage .   

 

   

G102 .1

Battery test

1.  Remove AC Input for two minutes.
2.  Measure Vdc of battery with no load present - positive 

probe to P1-2 (B+), negative probe to P1-5 (B-, ground) 

(See Figure 2). If less than 23.3 volts, charge battery for 

24 hours.

3.  Push white Battery Test push button. 

otee:

N

Voltage drop should not exceed two volts.

Lamp test

Push the LAMP TEST (white) pushbutton to check indicator 

operating lights. This energizes all lights simultaneously. The 

remote status and operating contacts are not tested.

941197KM

9

OPERATION INSTRUCTIONS

   MN285018EN   May 2017

DC motor operator control installation and operation instructions

Summary of Contents for COOPER POWER SERIES

Page 1: ...DC motor operator control installation and operation instructions COOPER POWER SERIES Padmounted Switchgear MN285018EN Effective May 2017 Supersedes October 1994 S285 80 1...

Page 2: ...OSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NO...

Page 3: ...iliary contacts 2 Simultaneous indication for SCADA 2 Electrical interlocks 2 Control operation LOCAL Mode 3 LOCAL Mode operation 3 LOCAL Mode features 3 Battery charger board 3 Wiring schematic 4 Ins...

Page 4: ...Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around hig...

Page 5: ...that the battery is disconnected during storage Quality standards ISO 9001 Certified Quality Management System Control battery storage and charging The 24 Vdc control battery is fully charged prior t...

Page 6: ...panel With the SCADA switch on REMOTE STATUS and control functions are accessed via the SCADA interface See Figures 4 and 6 Auxiliary contacts One a and one b auxiliary switch contact from the B phas...

Page 7: ...rupter mechanism via the motor operator STOP YELLOW PUSH BUTTON Stops the motor operated opening or closing action of the selected switch or interrupter mechanism Note N Mechanisms should not be left...

Page 8: ...Figure 4 Wiring schematic of DC motor operator control 4 OPERATION INSTRUCTIONS MN285018EN May 2017 DC motor operator control installation and operation instructions...

Page 9: ...agrams supplied with your control for specific information on accessories or special modifications that were supplied at the time of manufacture Dashed wires indicate customer made connections 5 OPERA...

Page 10: ...h SCADA terminals Select one of several motors Read status of selected motor Operate the selected motor Monitor opening or closing action REMOTE Mode Features All remote features are accessed through...

Page 11: ...set to the LOCAL position for extended local control operation CLOSE RED PUSH BUTTON Closes the selected switch or interrupter mechanism via the motor operator OPEN GREEN PUSH BUTTON Opens the select...

Page 12: ...Figure 7 Outline diagram of DC motor operator control 8 OPERATION INSTRUCTIONS MN285018EN May 2017 DC motor operator control installation and operation instructions...

Page 13: ...onnects the motor to the yellow handle See Figure 11 Translator Tube Figure 10 DC Motor actuator disconnected Note N The actuator and limit switches are adjusted for proper operation prior to shipment...

Page 14: ...ical operating characteristics of the DC Motor Operator Control Table 1 DC motor operator ratings Close max amps Open max amps Running load amperage RLA 12 12 Lock rotor amperage LRA 24 23 In rush 20...

Page 15: ...This page intentionally left blank 11 OPERATION INSTRUCTIONS MN285018EN May 2017 DC motor operator control installation and operation instructions...

Page 16: ...tes Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN285018EN May 2017 KA2048 0406 REV01 Eaton is a registered trademark All trademarks are property of their...

Reviews: