Figure 32. Installing to connecting plugs.
In su lat ing Plug
Connecting Plug
Connecting Plug
Connecting Plug
Drain
Wire
Drain
Wire
5/16" Hex
Shaft
1" Wrench
Torque
Wrench
Socket
Wrench
Figure 33. Last insulating plug installation.
In su lat ing Plug
Insulating
Plug
Torque
Wrench
Connecting Plug
Drain
Wire
Drain
Wire
•
Repeat the previous assembly procedures for each
additional splice tap. (Refer to Figure 32.)
•
After the last connecting plug and T-body are installed,
obtain the second insulating plug. If stud has not
been factory installed, hand thread a 5/8" stud into the
insulating plug.
•
Install the second insulating plug, with stud, into the
open interface of the last T-body. Hand thread the
insulating plug into the connecting plug.
•
Secure the first insulating plug using a 1" wrench. Using
a 1" socket on a torque wrench, tighten the second
insulating plug to 55 ft-lbs. (Refer to Figure 33.)
•
Clean and lubricate the inner surface of two insulating
plug caps with the lubricant supplied.
•
Push the caps onto the insulating plugs until they snap
into place.
•
Connect one drain wire to the tie-off tab of each T-body
and connect the other end to a common ground point.
ote:
N
If splice is disassembled, all connecting plugs and
insulating plugs should be completely removed,
cleaned, regreased, and reassembled following
the above procedure to ensure connection points
are properly torqued.