background image

IF 1700  •  02/14 

                         Copyright © 2014 Eaton’s Crouse-Hinds Business  

Page 1

EVHF106 Series Portable Lighting

Fixture for Hazardous Locations

Installation & Maintenance Information

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

IF 1700

APPLICATION

The EVHF106 S714 portable hand lamp is used to 

provide task lighting in hazardous (classified) locations. 

When properly installed, EVHF106 hand lamps are 

suitable for use in Class I, Groups C, D (26 watts 

maximum) and Class II, Group G (26 watts maximum) 

locations as defined by the National Electrical Code

®

The standard EVHF106 S714 hand lamp is designed for 

use with #16/3 type SOOW portable cord only. Portable 

cord to be: 90

º

C 600 Volt UL/CSA, current Amps 

13.  Cord size 0.390-0.625.  Cord is to be supplied by 

installer.  Cord to be rated “Extra Hard Usage” (per 

NEC501.140(B)(1). 

Note:

 This portable lighting fixture include a 26W 

compact fluorescent lamp (Type: Energy Saver T2, 

Model: EL-md T2 26W) by Phillips.

DISASSEmbLy FOR wIRINg & LAmPINg

1.   Loosen handle locking set screw (1) and unscrew 

black plastic handle assembly (2) from guard and 

globe assembly (3).  DO NOT disassemble the 

metal ring and glass globe.

2.   Loosen cord clamp (7) from connector housing (8) 

by loosening the two attachment screws (9).

3.   Remove locking screw (10) that holds the handle 

and connector housing together.  Save this locking 

screw for later replacement.

4.   Unscrew the connector housing from the handle.

wIRINg AND REASSEmbLy

1.   Insert end of #16/3 type SOOW cord (11) through 

cord support bushing (6), connector housing (8), 

spacer (5) and cord grip assembly (4).  (Loosen 4 

screws on cord grip assembly just short of removal 

and push cord through grips approximately 6 

inches).

2.   Remove outer covering of cord 7/8” and strip end 

of each wire in the cable 3/8” for connections to 

the three pressure connectors (12) as follows:

a.   Attach grounding wire (green) to terminal marked 

“G” (green colored connector).

b.   Attach grounded wire (white) to terminal marked 

“W” (nickel plated connector).

c.   Attach third wire (black) to the remaining terminal 

(copper).  Make certain there are no loose strands 

of wire outside the connectors.

3.   Slide cord grip assembly toward handle to engage 

locating notches in handle.

wARNINg

DO NOT disassemble the cast metal guard/glass 

globe assembly.  Disassembly of the globe portion of 

the hand lamp is limited to removing the guard/globe 

assembly from the black plastic handle assembly.

CAUTION

Use only #16/3 type SOOW portable cord with 

EVHF106 S714 hand lamp.

4.   Make sure cord insulating jacket extends fully 

through cord grip assembly (push down on cord) 

and tighten 4 screws in cord grip assembly.  If 

the 4 screws were removed during disassembly, 

be sure the indicating arrows are properly aligned 

when reassembling and tightening.

5.   Slide spacer against cord grip assembly.

6.   A silicone base lubricant has been applied at the 

factory on “O” ring and handle threads of black 

plastic handle assembly (2).  Reapply if required.

7.   Make sure cord grip assembly is properly 

positioned on locating notches in handle.  Thread 

connector housing (8) fully over handle.

8.   Replace locking screw (10) in handle.

9.   Slide cord support bushing (6) tight against spacer, 

protruding through connector housing.

10.  Fully tighten screws (9) on cord clamp (7), onto 

connector housing (8).

11.  Install lamp in lamp holder (See nameplate for 

proper lamp designation and wattage) and securely 

tighten lamp into place.

12.  Replace guard and globe assembly onto handle 

until fully and completely tightened.

13.  Securely tighten the handle locking set screw.

mAINTENANCE

1.   The glass globe should be cleaned on a regular 

basis to maintain optimum lighting performance.

2.   At the time of cleaning, inspect globe and guard 

for tightness.  If loose, retighten and lock with set 

screw.

3.   Check cord for abrasion, cuts, or breaks.  Replace if 

necessary.

4.   Perform visual, electrical, and mechanical 

inspections on a regular basis. This should be 

determined by the environment and frequency 

of use; however, it is recommended that a 

check should be made at lease once a year.  We 

recommend an Electrical Preventative Maintenance 

Program as described in the National Fire 

Protection Association Bulletin NFPA No. 70B.

Note: 

For this portable lighting fixture use Phillips 

compact fluorescent lamps type Energy Saver 

T2. Models: EL-md T2 23W & EL-md T2 26W) by 

Phillips.

All  statements,  technical  information  and  recommendations  contained  herein  are  based  on  information  and  tests  we  believe  to  be 

reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Crouse-Hinds “Terms and Conditions of Sale,” 

and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use 

and assumes all risk and liability whatsoever in connection therewith.

   

 

 

Eaton’s Crouse-Hinds Business 

 

IF 1700

 

 

 

 

 

1201 Wolf Street Syracuse, New York  13208  •  USA 

Revision 1

 

 

 

 

 

Copyright © 2014 

New 02/14

wARNINg

All electrical power must be turned off before and 

during maintenance.

wARNINg

Globe is tempered explosionproof glass and if 

scratched or chipped it must be immediately 

replaced to prevent equipment and/or personal 

damage or injury.

CAUTION

Globe/guard assembly is factory sealed and must not 

be disturbed.  For globe replacement, please contact 

your Crouse-Hinds ECM Sales Representative or the 

Sales/Service Department in Syracuse.

globe & 
guard
Assembly

Handle 
Locking Set 
Screw

Locking 
Screw for 
Connector 
Housing

Handle 
Assembly

3 Pressure 
Connectors

Connector 
Housing

Cord
Clamp

Screws

Cord 
Support

Cord

Cord grip
Assembly

Spacer

1.

2.

8.

9.

10.

3.

4.

5.

6.

7.

12.

11.

Reviews: