background image

6

4.1  Opening and closing the light fitting

–   Unscrew the four screws of the cover. 
–   The cover can be opened to the molded-on 

hinges. For ease of installation, the cover can 
be removed out of the hinges. If putting 
down take care to prevent scratches on the 
silk screen cover.

4.2  Installation of the fitting

 

Warning. Hazard due to electrostatic 

charges! 
Luminaire must not be installed in the 
vicinity of charge-generating processes!

The luminaire shall be fitted by using the four 
mounting clips with suitable fixing screws   
(Ø 5 mm, fig. 1) onto a suitable surface.

4.3 Mains connection

Open the cover as described. 

Pass the cable (5.5 to 13 mm) through the 
certified Ex cable entry M 20 x 1,5. Use both 
sealing inserts for cables from 7 to 9 mm, and 
the outer sealing insert only for cables from 9.5 
to 13 mm. Pay attention to the proper fit of the 
remaining sealing insert in the certified  cable 
gland. 

In case of unused cable entries, remove their 
protective cover and close the entries with a 
blanking plug (torque of 1,7 Nm). When closing 
the gland with a blanking plug, always use both 
sealing inserts! When metal cable entries are 
used, the protective caps of the unused entries 
are to be removed and the entries to be closed 
with certified Ex blanking plugs!

 

Only fix laid cable may be used for 

connection! If cable glands from other 
manufacturer  are used the instructions 
regarding strain relief and clamping capacity 
must be observed!

Connect the conductors to the terminals L, N 
and  PE in accordance with the terminal 
marking (see fig. 2). 

Remont the LED-printed board into the 
housing. 

Take care not to pinch any conductors. Install 
the protective cover with the four screws. 
Tighten the screws only hand-tight!

5.  Monitoring (only EXIT V-CG-S)

The V-CG-S module monitors and indicates to 
the connected CEAG emergency supply system 
the operation of the supply unit circuit and the 
function of min. 50 % of the installed LEDs.

The V-CG-S module allows single monitoring of 
these luminaires in CEAG emergency lighting 
systems. The switching mode (maintained/
non-maintained and switched emergency  
luminaires) is freely programmable and mixed 
operation up to 20 addresses in a single circuit  
is possible.

5.1 Addressing

Before fitting the cover, the addressing of the 
individual luminaires is to be carried out. The 
desired address (fig.4, 1 - 20) is set on the 
address switch by means of a suitable screw 
driver (Arrowhead to No., fig. 3). If the luminaire 
should not be monitored the code 0/0 has to be 
selected. 

The standing luminaire EXIT and is not 
equipped with monitoring circuit and can not be 
addressed.

6.  Taking into operation

 

Prior to operation, check the light fitting 

for its proper functioning and installation in 
compliance with these operating instruc-
tions and other applicable regulations!

Only carry out insulation measurements 
between PE and the external conductor L as 
well as between PE and N.

 

  – measuring voltage: max. 1 kV AC/DC 

 

  – measuring current: max. 10 mA

 

There must no insulation measurement 

be carried out between L and N, since that 
would destroy the electronics (mains input 
fuse in the unit).

GB

Explosion protected LED-exit luminaire 
Series: EXIT, EXIT 24 V and EXIT V-CG-S

7. Maintenance

 

Observe the national regulations 

applicable to the maintenance, servicing and 
test of apparatus for explosive atmospheres 
e.g IEC/EN 60079-17 as well as the general 
rules of engineering!

7.1 Servicing

When servicing, in particular those components 
that affect the explosion protection, will have to 
be checked, e. g.:
–   Housing and protective bowl for any cracks or 

damages.

–   Gaskets for their perfect condition.
–   Terminals and blanking plugs for their firm fit.
–   Because of the risk of an electrostatic charge, 

the light fitting shall only be cleaned with a 
damp, non-fibrous  cloth or sponge! 
Only use customary household washing-up 
liquid diluted in water as specified! The water 
temperature may be max. 50°C. 
After that, rinse with clear water to prevent 
the risk of tension cracks in the protective 
bowl!

7.2 Repair

Prior to replacing or removing any components, 
observe the following:

Cut the apparatus off the voltage before 
opening it or carrying out repairs!  Only use 
certified genuine CEAG/CCH spare parts! (See 
CEAG/CCH spare parts list).

Subject to alteration or supplement of this  
product series.

Regarding waste disposal, observe the relevant 
national regulations! The plastic materials are 
marked with material identifi cations.

Summary of Contents for CROUSE-HINDS EXIT Series

Page 1: ...del manuale operativo in un altra lingua della Comunit Europea potete richiederla al vostro rappresentante Cooper Crouse Hinds CEAG LT ios naudojimo instrukcijos i verstos J su gimt j kalb galite pare...

Page 2: ...drawings Plans cot L N PE PE N L 2 1 Pfeil Arrowhead Fl che Befestigungsschrauben Fixing screws vis de fixation 5 mm Bild 3 fig 3 Fig 3 Bild 2 fig 2 Fig 2 Netzanschluss Mains connec tion sch ma des co...

Page 3: ...S 1 Legende Warnung Dieses Symbol warnt von einer ernsten Gefahr DieseWarnung nicht zu beobach ten kann Tod oder die Zerst rung von Einrichtungen zur Folge haben Achtung Dieses Symbol warnt von einem...

Page 4: ...chtversorgungs systemen betrieben werden Hierbei kann der Betreiber die Schaltungsart frei programmieren So k nnen an einem Endstromkreis bis zu 20 Leuchten in unterschiedlichen Schaltungs arten betri...

Page 5: ...ntry Standard version M20 x 1 5 for cable 7 to 13 mm suitable cables and test torques of the pressure srew Nm seel 1 2 1 2 min max 1 2 7 0 9 0 1 5 1 4 seel 2 1 2 min max 2 9 5 13 0 1 0 1 7 metal M20x1...

Page 6: ...rogrammable and mixed operation up to 20 addresses in a single circuit is possible 5 1 Addressing Before fitting the cover the addressing of the individual luminaires is to be carried out The desired...

Page 7: ...mbole avertit d un danger grave Le non respect de cet avertissement peut entrainer la mort ou la destruction de biens Ce symbole met en garde contre un ventuel d faut Le non respect de cette consigne...

Page 8: ...soient conformes aux instructions de cette notice d utilisation et toutes les autres prescripti ons en vigueur Les mesures d isolation ne doivent tre effectu es qu exclusivement entre PE et les c ble...

Reviews: