88
Explosion protected plug and socket system 16 A,
3-pole, 4-pole, 5-pole, GHG 511
1
Technical data
ATEX type examination certificate /
IECEx Certificate of Conformity:
Wall socket
GHG 511 4.
BVS 17 ATEX E 053 X
IECEx BVS 17.0045 X
Plug
GHG 511 7.
BVS 17 ATEX E 053 X
IECEx BVS 17.0045 X
Coupler
GHG 511 3.
BVS 17 ATEX E 053 X
IECEx BVS 17.0045 X
Flange socket
GHG 511 8.
BVS 15 ATEX E 101 U
IECEx BVS 15.0088 U
Plug
GHG 543 2.
PTB 99 ATEX 1039
IECEx BVS 04.0002
Plug
GHG 531 7.
PTB 99 ATEX 1039
IECEx BVS 04.0002
Marking acc. to 2014/34/EU and
the series of standards EN 60079:
D
II 2 G Ex db eb [ia] IIC / IIB / IIB+H2 T6 / T5 Gb
D
II 2 D Ex tb IIIC T80 °C Db
Flange socket GHG 511 8
D
II 2 G Ex db eb IIC / IIB / IIB+H2 Gb
D
II 2 D Ex tb IIIC / IIIB Db
Category of application and the series of standards IEC 60079:
Ex db eb [ia] IIC / IIB / IIB+H2 T6 / T5 Gb
Ex tb IIIC T80 °C Db
Rated voltage:
GHG 511 -
3-pole
up to 415 V, 50/60 Hz; max 400 Hz
GHG 511 -
4-pole
up to 690 V, 50/60 Hz; max 400 Hz
GHG 511 -
5-pole
up to 690 V, 50/60 Hz; max 400 Hz
Plug GHG 543 2.
up to 250 V, 50/60 Hz
Plug GHG 531 7.
up to 690 V, 50/60 Hz
(Special voltages and various contact-marking are possible on request.)
Gasgroupe
Perm. ambient temperature:
IIB
IIB+H
2
IIC
X
ATEX - IEC
Install protected against
higher mechanical risk. Max 4J
Type
maximum rated current
Wall socket GHG 51.4...R.... / Flange socket GHG 51.8...R.... / 3p (default temperature range)
..
16 A
-
-
-45 °C ... +55 °C
-
16 A
-
-30 °C ... +55 °C
-
-
16 A
-20 °C ... +55 °C
Wall socket GHG 51.4...R.1.. / Flange socket GHG 51.8...R.1.. / 3/4/5p (Extendet temperature range)
16 A
16 A
-
-55 °C ... +45 °C
10 A
10 A
-
-55 °C ... +55 °C
-
-
16 A
-20 °C ... +45 °C
-
-
10 A
-20 °C ... +55 °C
Wall socket GHG 51.4...R.... / Flange socket GHG 51.8...R.... / 4/5p (default temperature range)
16 A
16 A
-
-55 °C ... +55 °C
-
-
16 A
-20 °C ... +55 °C
Coupler GHG 51.3...R....
16 A
16 A
16 A
-20 °C ... +55 °C
Plug GHG 51.7...R.... (
min. 2.5 mm²)
16 A
16 A
16 A
-40 °C ... +45 °C
-55 °C ... +45 °C
Plug GHG 51.7...R.... (
min. 4.0 mm²)
16 A
16 A
16 A
-40 °C ... +55 °C
-55 °C ... +55 °C
Plug GHG 51.7...R.... (
min. 2.5 mm²)
10 A
10 A
10 A
-40 °C ... +55 °C
-55 °C ... +55 °C
Stecker GHG 51.7...R.... (
1,5 - 2,5 mm²) (
4,0 mm²)
16 A
16 A
16 A
-20 °C ... +40 °C
-55 °C ... +40 °C
Plug
GHG 543 2. / GHG 531 7.
16 A
16 A
16 A
-20 °C ... +40 °C
(Special versions permit deviating temperatures)
Back-up fuse:
GHG 511
GHG 543/531
without thermal protection
20 A
16 A
with thermal protection
35 A gG
32 A gG
Switching capacity AC 3
3-pole:
250 V/16 A
Switching capacity AC 3
4-pole:
400 V/16 A
Switching capacity AC 3
5-pole:
500 V/16 A
Protection category acc. to EN/IEC 60529
IP 66 (catalogue version)
(1)
(1)
with closed and secured hinged cover as well as combinations properly plugged together.
Attention! When the Plugs GHG 543/531 is insert with sockets of the series GHG 511,
the "IP" protection category of the combination is reduced to the minimum protection category "IP 54".
Insulation class acc. to IEC/EN 61140:
I – with metal flange or metal cable entries
II - is complied with by devices
GB
Summary of Contents for Crouse-Hinds GHG511 Series
Page 22: ...22 Notizen Notes Remarques ...
Page 23: ...23 Notizen Notes Remarques ...