background image

5

INM F890 Rev 1

Press the carrier onto the DIN-rail and rotate each of the DIN clamp screws clockwise 
until the tab tightens against the DIN-rail.  The clamping tabs can be seen through the 
Inspect clamps holes when they are in the correct position.

4 .4  Removal from DIN-rail

The Power Modules must be removed from the carrier to obtain access to the DIN-
rail clamp screws.  Support the carrier by pressing it to the DIN-rail and unscrew 
(counterclockwise) the six DIN-rail clamp screws. Turn each screw approximately two 
full turns when releasing its clamping tab from the rail. Remove carrier.

4 .5  Mounting and Removal of the Power Modules

The Power Modules are secured to the carrier with four screw mountings.  There are 
four locating connectors (two for each module) on the module carrier along with mating 
connectors in the F801 or F802 module.  Align the module with the retaining screws 
and press onto the connector.  Hold it in place while tightening the four retaining 
screws.  To remove a Power Module, support the module while unscrewing the four 
retaining screws at its base.  Lift the module off the carrier connector.

Note:  Earlier versions of the module carriers do not have locating connectors.  Align 
using the retaining screws furthest from the module connector and rock onto the 
connector. 

ELECTRICAL CONNECTIONS

       

Figure  4 -

 Electrical Block Diagram of F890-CA

Megablock

wiring hub

 F801 or F802

Power Module A

 F801 or F802

Power Module B

Power B

Power A

To fieldbus devices

To fieldbus

segments

   2 - 8

1

2

3

4

5

6

7

8

To Host Ports

     1 - 8

1

2

3

4

5

6

7

8

Summary of Contents for Crouse-Hinds MTL F890

Page 1: ...MTL F890 8 Segment Redundant Fieldbus Power Supply for use with non proprietary cabled systems March 2022 INM F890 Rev 1 Instruction manual MTL fieldbus networks...

Page 2: ...ii INM F890 Rev 1 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 3: ...5 5 ELECTRICAL CONNECTIONS 5 5 1 DC Power Requirements 6 5 2 Power A and Power B 7 5 2 1 Redundancy 7 5 2 2 Terminator 7 5 3 Alarm Connection 7 5 4 FInal Segment Connections 8 5 5 Field Segment Conne...

Page 4: ...dule may be used where redundancy is not required 2 DESCRIPTION For maximum reliability the module carrier contains no components and only provides interconnections between the Power Modules and the e...

Page 5: ...xtinguished and the red Alarm LED is lit Redundant 24V DC nom input power is connected to the F890 CA carrier using two part pluggable connectors Field wiring connections are available with either plu...

Page 6: ...s www mtl fieldbus com Relcom Inspect Clamps Inspect Clamps Shield Ground Option Ground SG 51 52 53 Rev E 0 S S S S S S S S 20 21 22 17 18 19 14 15 16 11 12 13 23 24 25 26 27 28 29 30 31 32 33 34 Segm...

Page 7: ...ure that the permitted ambient temperature range of 40 C to 65 C derate to 50 C for the F802 when loaded above 60 of its full load rating is not exceeded Allow for power dissipation within the enclosu...

Page 8: ...carrier with four screw mountings There are four locating connectors two for each module on the module carrier along with mating connectors in the F801 or F802 module Align the module with the retaini...

Page 9: ...vided allowing the use of bulk power supplies with a supply range of 19 2 30VDC Input power cabling and over current protection devices must be chosen to match the current consumption An F890 system o...

Page 10: ...ion Power must be connected to Power B terminals if live replacement of Power Module A is necessary since Power B terminals feed the Power Module B connector 5 2 2 Terminator A single terminator is pr...

Page 11: ...28 Segment 6 17 Segment 3 29 Segment 7 18 Segment 3 S 30 Segment 7 S 19 Segment 3 31 Segment 7 20 Segment 4 32 Segment 8 21 Segment 4 S 33 Segment 8 S 22 Segment 4 34 Segment 8 The host cable length s...

Page 12: ...the connector for the indicated function When using the screen grounding facility on the F890 carrier the jumper must be installed correctly Figure 7a and an Instrumentation Ground must be routed to...

Page 13: ...ith nine LEDs eight to indicate segment status and one to signify an Alarm condition Fault Condition Segment LED Fault Alarm contact status No Fault Green Off Closed Segment shorted Off Red Open Outpu...

Page 14: ...11 INM F890 Rev 1 8 FM CONTROL DRAWINGS...

Page 15: ...ed in place of the missing F801 or F802 module 24VDC Power Supplies may be installed in the Non hazardous area Vmax 24VDC F801 30VDC F802 24VDC Power Supply A 24VDC Power Supply A This is a Chassis Gr...

Page 16: ...clause 4 2 of EN 60079 17 b This equipment has been designed to provide protection against all the relevant additional hazards referred to in Annex II of the directive such as those in clause 1 2 7 c...

Page 17: ...ified product 9 5 Marking Each device is marked in compliance with the Directive Regulation This information applies to products manufactured during or after the year 2007 Typical certification markin...

Page 18: ...15 INM F890 Rev 1 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 19: ...Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia srl Via San Bovio 3 20090 Segrate Milano...

Reviews: