background image

I.B. 48003

Page 15

Effective 11/97

For Contactor. Be sure that:

1.

THE FOUR PHASE BARRIERS ARE INSTALLED
WHEN PROVIDED.

2.

The contactor coil is electrically isolated, to prevent
feedback into a control power transformer and a
hazardous situation.

3.

There has been a check, using an extension cord
and a separate source of AC control circuit power, of
the control circuit functions.

Operate the appropriate pushbuttons to close and open
the contactor.  If the contactor does not close fully or
does not drop out fully, refer to the CONTACTOR MAIN-
TENANCE
 section below.

While the contactor is closed, observe the overtravel gap
between the pivot plates on the cross bar and the underside
of the lower bottle nut on each pole.  This overtravel gap
should be no less than .075 inch (1.91 mm) when the
contactor is new.  If less, refer to Contact Wear Allowance.

While the contactor is open, push the armature rearward
with a long screwdriver or other rod applied to the lower
end of the armature above the coil terminals.  The
armature should not move because it should be firmly
against the glass polyester main frame.  See Figure 11.
To correct a problem, see Changing Operating Coil
under CONTACTOR MAINTENANCE.

Disconnect the extension cord and restore the plug into
its socket on the contactor chassis.

CHECK-OUT, VACUUM INTERRUPTERS

The dielectric strength of the interrupters should be
checked before the contactor is energized for the
first time
 and regularly thereafter to detect at the earliest
possible date any deterioration in the dielectric strength
of the contact gap since this may result in an interruption
failure.  Although an AC dielectric test is recommended, a
DC test may be performed if only a DC test unit is
available.  A good vacuum interrupter will withstand a
16kV-60-Hz test or a 23kV-DC test across a .156-inch
(4-mm) contact gap.  This is the nominal contact gap for a
new contactor.  When performing DC tests, the voltage
should be raised to test value in discrete steps and held
for a period of one minute.  When tested with an AC high
potential tester, expect a capacitance leakage current of
approximately 1.3 milliamperes.  For a DC tester expect
5 microamperes.  Any spark across the contact gap
indicates failure.

SOME DC HIGH POTENTIAL UNITS, OPERATING AS
UNFILTERED HALF-WAVE RECTIFIERS, ARE NOT
SUITABLE FOR TESTING VACUUM INTERRUPTERS,
BECAUSE THE PEAK VOLTAGE APPEARING
ACROSS THE INTERRUPTERS CAN BE
SUBSTANTIALLY GREATER THAN THE VALUE
INDICATED.

When a vacuum bottle is tested with voltage over 5000
volts across its open gap, there is some possibility of
generating X-rays.  Test time should be minimized, and
personnel should not be closer than 10 feet (3 meters)
and preferably located behind some barrier.  This is a
precaution until such time as the possible hazard is better
understood and standards are published.

Periodic dielectric tests across open contacts should not
be omitted on the basis of satisfactory contactor perfor-
mance since under certain operating conditions, the
contactor may perform satisfactorily even though one
vacuum interrupter has become defective.

The interval between periodic tests depends on the
number of operations per day, environmental factors, and
experience.  It is a matter of operator judgment.

CHECK-OUT, MECHANICAL

One of the features of Ampgard

®

 motor control is the inter-

locking of the contactor and isolating switch which prevents
opening the isolating switch when the contactor is closed,
and prevents closing the isolating switch if the contactor is
already closed due to some malfunction. Neither closing nor
opening of the isolating switch under load is permissable.
The isolating switch interlock arm does not move, except
when the isolating switch is being opened or closed.

Similarly, during the opening or closing of the isolating
switch, the interlock rod on the isolating switch drives the
interlock arm of the SJS contactor clockwise so that the
heavy end moves down to keep the contactor from
closing.  If the isolating switch interlock rod is not attached
to the interlock arm of the contactor by the clevis shown in
Figures 7 and 8, the natural weight of the interlock arm
moves the arm to a position which prevents the contactor
from closing.

All these interlocks are intended to protect against mal-
function.  But they should be tested with main POWER
OFF prior to start-up (and at intervals thereafter) by
simulating improper operation and sequencing of the
contactor and isolating switch.  Failure to interlock must be
corrected before power is applied.

CAUTION

Summary of Contents for Cutler-Hammer Ampgard SC9000

Page 1: ...shown in Table I The controller may also be used to switch transformer windings or capacitor banks Each Ampgard controller occupies all or a portion of a steel structure that may also enclose a horizontal bus system to distribute power to two or more sections and a vertical bus system in each section con nected to the horizontal main bus system The controllers are configured for full voltage or re...

Page 2: ...ch See Figure 2 Connect the conductors from the motor to these latter terminals LOW VOLTAGE CONTROL COMPONENTS The low voltage components consisting of an interposing relay protective relays and optional equipment are generally mounted on a slide out panel The single phase control power transformer is bolted to the contactor frame The capacity of this transformer ranges from 600 VA to 2 kVA depend...

Page 3: ...I B 48003 Page 3 Effective 11 97 Fig 4 Ampgard Components Two Starters Controllers Shown ...

Page 4: ... mounted between phases and also between the two outside poles and the isolating switch end plates This isolating switch is a nonload break device It must never close or interrupt a power load However it does have a limited capacity for interrupting the single phase control power and potential transformers exciting current In terms of transformer ratings the maximum load is the equivalent of an un...

Page 5: ...tor is 7600 amperes r m s symetrical The current transform ers overload protector and power circuit fuses are coordinated with the motor characteristics so that the controller must be used with the motor for which it was designed Motors with special characteristics often require additional protective relays Consult the instruc tion leaflet for that particular protective relay before attempting any...

Page 6: ...witch Interlock There is also a mechanical interlock that is designed to prevent the isolating switch from closing with the contactor already closed and to prevent the contactor from closing while the isolating switch is being opened This latter state the transition phase is shown in Figure 7 With the isolating switch fully open or fully closed the contactor may be opened or closed See Figure 8 If...

Page 7: ...for each pole of the contactor A three pole contactor has three vacuum bottles A metal bellows like a small circular accordion allows the moving contact to be closed and pulled open from the outside without letting air into the vacuum chamber of the bottle Both the bellows and the metal to ceramic seals of modern bottles have been improved to the point that loss of vacuum is no longer cause for un...

Page 8: ... fuses are mounted directly above the contactor as for example in the case of one contactor in a reversing controller no barriers are required or furnished CONTACTOR MOUNTED COMPONENTS To simplify installation and servicing a number of related components are mounted on the Type SJS contactor chassis a control power transformer with test plug and fuses instrument quality potential transformers with...

Page 9: ...I B 48003 Page 9 Effective 11 97 Fig 11 Type SJS Contactor Positions ...

Page 10: ... barriers for easier access To reinstall reverse the procedure INSTALLATION This industrial type control is designed to be installed by adequately trained and qualified personnel with appropri ate supervision These instructions do not cover all details variations or combinations of the equipment its storage delivery installation check out safe operation or maintenance Care must be exercised to com...

Page 11: ...low voltage cables may be conveniently arranged near the right hand enclosure wall See Figure 3 G ISOLATING SWITCH H ISOLATING SWITCH AUXILIARY CONTACT TERMINAL BLOCKS J ISOLATING SWITCH MECHANICAL INTERLOCK K FUSE PULLER L LOAD CABLES M MOTOR TERMINALS A POSITIONING BOLTS B POWER CIRCUIT FUSES C MEDIUM VOLTAGE COMPARTMENT DOOR D CONTROL TERMINAL BLOCKS E VACUUM CONTACTOR F LOW VOLTAGE COMPARTMENT...

Page 12: ...ge door C 3 Separate the contactor side of the control wires from the terminal block D 4 Disconnect the auxiliary contact terminal blocks H on the isolating switch 5 Remove contactor E with a sharp pull forward 6 Part way out the contactor will reach a balanced position Lower the contactor to the floor and slide it out of the way The contactor weighs approximately 160 lbs 73 kilograms If a contact...

Page 13: ... shown 10 Refer to load cable instruction tag located at motor terminals M for load wiring instructions Controller is now ready to wire both line and load 11 After wiring reverse the procedure to reassemble Slide the isolating switch in place and secure with two bolts Refer to Steps 7 and 8 12 Check to make sure each fuse clamp is in correct position in fuse locator Refer to instructions on the lo...

Page 14: ... material 6 THE INSULATION LEVEL OF THE STARTER IS CHECKED AND RECORDED BEFORE THE STARTER IS ENERGIZED See GENERAL MAIN TENANCE 14 Reconnect the clevis attached to the mechanical interlock arm Reconnect the isolating switch auxiliary contact terminal blocks Reconnect the contactor control wire terminal blocks Refer to Steps 3 and 4 15 Install the three power circuit fuses Make sure each fuse is f...

Page 15: ...eres Any spark across the contact gap indicates failure SOME DC HIGH POTENTIAL UNITS OPERATING AS UNFILTERED HALF WAVE RECTIFIERS ARE NOT SUITABLE FOR TESTING VACUUM INTERRUPTERS BECAUSE THE PEAK VOLTAGE APPEARING ACROSS THE INTERRUPTERS CAN BE SUBSTANTIALLY GREATER THAN THE VALUE INDICATED When a vacuum bottle is tested with voltage over 5000 volts across its open gap there is some possibility of...

Page 16: ...practices c Be trained in rendering first aid d Be knowledgeable with respect to electrical installa tion codes and standards for example the National Electrical Code NEC MAINTENANCE PROGRAM A maintenance program should be established as soon as the controller has been installed and put into opera tion After the controller has been inspected a number of times at monthly intervals and the condition...

Page 17: ...same manner and record Investi gate any abrupt reduction in resistance or any unusually low reading Dust and moisture are detrimental to electrical equipment and industrial equipment is designed to tolerate a less than perfect environment However excessive dust can cause trouble and should be wiped or blown off at appro priate intervals If the contactor is wet for any reason dry it until the insul...

Page 18: ... service after a fault However if there is no physical evidence of stress and if the overtravel exceeds the 020 inch 51 mm minimum the bottles can then be dielectrically tested as outlined previously If physical stress overtravel and dielectric test results are within acceptable limits it is reasonable to return the contactor to service after a fault Magnet Operating Range When properly adjusted a...

Page 19: ... for mechanical interference that prevents the magnet from sealing If there is no interference then the magnet itself may be misaligned The magnet gap can be seen from the left and the right sides with the help of a flashlight The stationary magnet can be aligned with a 0 50 inch 12 7mm diameter steel rod inserted into the two holes in the core of the magnet and used as a lever to put a corrective...

Page 20: ...bending the operating arm with the forked end of the bottle wrench See Figure 15 After an L63 auxiliary contact is replaced gap adjustment may be made by first loosening the jam nut on the operating arm with a 0 438 inch open end wrench The gap size is changed by rotating the 0 25 20 bolt Clock wise rotation will increase the gap distance Counter clockwise rotation will decrease the gap distance U...

Page 21: ...I B 48003 Page 21 Effective 11 97 Fig 16 Cable and Connection Diagram ...

Page 22: ... It is designed to hold the insulating shutter closed This latch may be deliberately by passed and the shutter moved to the open position Caution should be observed since the exposed line terminal stabs of the starter may be energized at line potential When the isolating switch is replaced in the structure the latch lever is automatically released to allow the shutter to operate normally Lubricati...

Page 23: ...tenance 16 Initial Insulation Level 16 Inspection After Short Circuit 18 Installation 10 Page Insulation Level 17 Isolating Switch 4 9 Isolating Switch Contactor Interlock 6 Isolating Switch Handle Positions 4 Isolating Switch Maintenance 22 Line Stab Insulating Shutter 6 Low Voltage Components 2 Low Voltage Cut Off Switch 4 Low Voltage Cut Off Switch Replacement 22 Lubrication 22 Magnet Operating...

Page 24: ...I B 48003 Page 24 Effective 11 97 Printed in U S A CCI Cutler Hammer 221 Heywood Road Arden NC 28704 ...

Reviews: