24
EATON CORPORATION Cutler-Hammer
Chiller Starter (AMPGARD) Technical Data TD02003003E Effective: October 2006
Reduced Voltage Autotransformer Starters Catalog S610
Non-Reversing
Mounted in the Medium Voltage Section
●
Three incoming line connectors.
●
One drawout 3-pole gang-operated line isolation switch assembly
with isolating shutter, external operating handle interlocked to
prevent opening the medium voltage compartment door until the
isolating switch is open and grounded.
●
Three vertically mounted current limiting power fuses with pop-up
blown fuse indicators.
●
One magnetic 3-pole vacuum contactor with dc operating coils
and mechanical interlock to prevent opening the isolation switch
when the contactor is closed.
●
One control power transformer (115-volt secondary).
●
Two CPT primary current limiting fuses.
●
One control circuit secondary fuse.
●
One run-test circuit.
●
Four electrical interlocks (2NO, 2NC).
Mounted in the Low Voltage Compartment
●
One control panel with:
– One MP-3000 motor protection relay
– Three interposing relays
●
One set of control circuit terminal blocks.
Reduced Voltage Structure(s)
●
One magnetic 3-pole vacuum run contactor with dc operating coil
and electrically and mechanically interlocked with the starting
contactor.
●
One magnetic 2-pole vacuum start contactor with dc operating coil
and electrical and mechanical interlocks.
●
Three current transformers.
●
One medium-duty starting autotransformer with 50 – 65 – 80% taps.
●
Three distribution class lightning arresters for high voltage stress
protection on the transformer zero tap.
Starting Characteristics
TABLE 13. TYPE 602 AUTO-TRANSFORMER STARTING
CHARACTERISTICS
Factory set on 65% tap.
FIGURE 13. STARTER ARRANGEMENT
Specifications
TABLE 14. STARTER SELECTION INFORMATION — DIMENSIONS IN INCHES (MM)
Horsepower based on NEMA standard design B motor at 1800 rpm.
When horizontal bus is added, height becomes 92 inches (2337 mm).
At higher hp rating, maximum acceleration time is 3.5 seconds.
At higher hp rating, maximum acceleration time is 6 seconds.
Note:
See
Figure 13
for Starter Arrangement diagram.
STARTER
TYPE
% MOTOR
VOLTAGE
% MOTOR
CURRENT
% LINE
CURRENT
% TORQUE
80% Tap
65% Tap
50% Tap
80
65
50
80
65
50
67
45
28
64
42
25
Auto
S
R
M
HORSEPOWER
VOLTS
CONTACTOR
AMPERE RATING
(ENCLOSED)
STARTER
INTERRUPTING
RATING (KVA)
DIMENSIONS
NUMBER OF
STRUCTURES
WEIGHT
LBS. (KG)
HEIGHT
WIDTH
DEPTH
2200 – 2400 Volts Non-Reversing
700/800
1500/1750
2300
2300
200
400
200,000
200,000
80 (2032)
80 (2032)
72 (1829)
72 (1829)
30 (762)
30 (762)
2
2
3100 (1407)
3100 (1407)
4000 – 4800 Volts Non-Reversing
1250/1500
2500/3000
4600
4600
200
400
400,000
400,000
80 (2032)
80 (2032)
72 (1829)
72 (1829)
30 (762)
30 (762)
2
2
3100 (1407)
3100 (1407)
6600 Volts Non-Reversing
2000/2250
4000/4500
6600
6600
200
400
570,000
570,000
80 (2032)
80 (2032)
72 (1829)
72 (1829)
30 (762)
30 (762)
2
2
3100 (1407)
3100 (1407)
Dimensions for estimating purposes only.