IL04915001E

 

 

 

Effective 7/09 

 

Ground fault circuit (cont’d) 

S/C Trip Level 

Current wave shape 

External CT 

Sine 

 

 

125 A ac 

IEC 60755 DC 0

°

 

110 A rms 

IEC 60755 DC 90

°

 

80 A rms 

IEC 60755 DC 135

°

 

60 A rms 

Accuracy of S/C trip Point  

±

 (10% + 2A) 

S/C Trip Delay 

±

2 ms 

Type 2 Co-ordination on S/C 

Selectable on / off with 0.02 and 0.3 s G/F Trip Delay 
settings 

Thermal withstand capability (external CT) 

300 A 

infinitely 

500 A 

2000 ms 

1000 A  500 ms 
2000 A  125 ms 
5000 A  20 ms 

Suitable external CT types – Must have 
internal electronics to provide short circuit/ 
open circuit detection 

5

 

C311CT1-A2 

46 mm (1.81”) inner diameter 

C311CT2-A2 

90 mm (3.54”) inner diameter 

C311CT3-A2 

150 x 170 mm (5.9 x 6.7”) Split core  

C311CT4-A2 

100 x 350 mm (3.94 x 13.78”) Split core  

C311CT5-A2 

145 mm (5.70”) inner diameter 

C311CT6-A2 

240 mm (9.45”) inner diameter 

C311CT7-A2 

300 x 300 mm (11.8 x 11.8”) Split core 

C311CT8-A2 

28 mm (1.1”) inner diameter 

C311CT9-A2 

65 mm (2.56”) inner diameter 

C311CT28-A2  28 mm (1.1”) inner diameter   

External CT Supervision circuit 

CT loop resistance causing a fault (O/C) 

> 1 k

 

CT shunt resistance causing a fault (S/C) 

< 50 

 

CT Fault Trip Delay 

1.5 s 

Relay contacts 

Configuration 

Voltage free form “Z” (1 N.O. and 1 N.C contact, 4 
terminals) 

Maximum UL/CSA rating 

5 A @ 125 and 250 V AC, general use 
1/6 hp, 125 and 250 V AC 
5 A @ 30 V DC, resistive 
B300: 
30 A, 3600 VA make, 3 A 360 VA break @ 120 V AC 
15 A, 3600 VA make, 1.5 A 360 VA break @ 240 V AC 
 

EN 60947 rating 

5 A @ 250 V ac, utilization category AC-12 
4 A @ 250 V ac, utilization category AC-13 
3 A @ 250 V ac, utilization category AC-14  
3 A @ 250 V ac, utilization category AC-15  
5 A @ 30 V dc, utilization category DC-12  
3 A @ 24 V dc, utilization category DC-13 
 

Isolation voltage 

2 kV rms, 50 – 60 Hz, 1 minute 

Breakdown voltage between open contacts 

1 kV rms 

Maximum fusing under EN 60947-5-1 

13 A 

                                                

5

 Future production of all Eaton C311CT Series 500:1 ratio CTs will be supplied with internal electronics to 

provide short circuit/open circuit detection by the D64RPB30 relay. These are designated Series A2, as shown 
above. They will work with all D64R relays suitable for 500:1 ratio CTs. 

 

Summary of Contents for Cutler-Hammer D64RPB30 Series

Page 1: ...l contactor contacts in the case of S C faults In this case the unit does not trip initially when the measured current exceeds the S C setpoint but waits for the upstream device to take care of curren...

Page 2: ...failed alarm state is As a result the red LED will now show the original cause of the trip 1 4 Reset Test pushbutton The built in momentary pushbutton is used to verify the condition of the D64RPB30 i...

Page 3: ...ontrol voltage is removed the relay will issue a 0 2 0 3 second pulse This means that when control voltage is restored after a trip due to loss of control voltage the contact will remain open This avo...

Page 4: ...ans that there is no electrical isolation between the control voltage input and the internal electronics As a result these share a common ground reference This reference is applied to the system throu...

Page 5: ...stalled beside the unit to act as the chassis ground point Use a minimum 14 AWG stranded conductor 6 For good EMC behavior it is important as in any installation to run all wiring especially if unshie...

Page 6: ...voltage 1 week minimum until the memory is read by pressing the Reset button Ground fault circuit G F Trip Level settable 0 03 0 10 0 50 1 2 3 5 9 A Accuracy of trip point 15 0 of Trip Level 3 G F Tri...

Page 7: ...8 A2 28 mm 1 1 inner diameter External CT Supervision circuit CT loop resistance causing a fault O C 1 k CT shunt resistance causing a fault S C 50 CT Fault Trip Delay 1 5 s Relay contacts Configurati...

Page 8: ...magnetic compatibility EMC for industrial process measurement and control equipment Part 4 2 Electrostatic discharge ESD immunity EN 61000 4 3 Electromagnetic compatibility EMC for industrial process...

Page 9: ...OURCE CURRENT CARRYING NEUTRAL WHEN USED GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire LOAD FIGURE 2 D64RPB30 TYPICAL FIELD CONNECTION WITH EXTERNAL 500 1 CURRENT TRANSF...

Page 10: ...1 38 35 2 36 60 2 76 70 1 38 35 Mounting hole Dia 0 22 5 5 DIN Rail Release 4 03 103 4 95 126 Dimensions Figure 3 Dimensions Drawing Approximate Dimensions in Inches mm Table 2 Approximate Dimensions...

Reviews: