EATON CORPORATION  Cutler-Hammer

   InformationSheets  70C1486H01

3

4.0 Remote Indicator

Circuit breakers built after July 2006 will be wired with
secondary contacts A12 which is reassigned to
Maintenance Mode Enable. (MM_E) - 

(See label on

secondary contacts)

 A normally open contact (A10, A11) is

available for customer use via programming of RelayA. This
contact can be used to indicate remotely that the
Maintenance setting is armed. Refer to diagram on page
three for a wiring of this remote (blue light) indicator.

5.0 Choosing the Reduction Setting

The Arc Flash Maintenance Switch has five unique
settings. From the factory, the Magnum circuit breaker is
shipped with the Digitrip unit set to the 2.5x setting and
with its Maintenance Mode disabled. The “Maintenance
Mode Enabled” message provides an indication that the
Maintenance Mode setting is armed per one of the  three
methods described in section 3.0.

In general, the selection of one of the Reduction Settings
should be determined and selected by a person who is

experienced in power system analysis.

This setting choice normally does not change unless there
are future system modifications that could increase or
decrease fault levels at the circuit breaker location.

For time/current curve information, refer to drawing
# 70C1498.

6.0  Tripping and Testing

The Maintenance Mode function will provide fast tripping
even when the regular Instantaneous is set to OFF. The
Instantaneous LED position is also used to indicate a trip
initiated by the Maintenance Mode setting. The message
“Maintenance Mode Trip” will be displayed after a trip.

The Maintenance setting, external wiring (if any) and
tripping functionality should all be periodically verified by
primary or secondary injection current testing.

FIGURE 2.  Digitrip 1150 with ARMs

Summary of Contents for Cutler-Hammer Digitrip 1150

Page 1: ...neral 2 2 0 Maintenance Mode Settings 2 3 0 Arming Maintenance Mode 2 4 0 Remote Indicator 3 5 0 Choosing the Reduction Setting 3 6 0 Tripping and Testing 3 Diagrams and Appendix Wiring Diagram 4 Display Matrix for Program Settings Menu 5 Display Matrix for Program Aux Relays Menu 6 Display Matrix for Program Accessory Bus 7 Display Matrix for Possible Events TRIP 8 Display Matrix for View Setting...

Page 2: ...S 2 0 Maintenance Mode Settings The Maintenance Mode Settings provide theArc Flash Reduction setting 2 5 x Rating Plug Value is the Maxi mum reduction setting which correlates to the lowest pickup value Available Trip current of Maintenance Mode Settings 2 5 x Rating Plug Amperes 4 0 x Rating Plug Amperes 6 0 x Rating Plug Amperes 8 0 x Rating Plug Amperes 10 0 x Rating Plug Amperes 3 0 Arming Mai...

Page 3: ... an indication that the Maintenance Mode setting is armed per one of the three methods described in section 3 0 In general the selection of one of the Reduction Settings should be determined and selected by a person who is experienced in power system analysis This setting choice normally does not change unless there are future system modifications that could increase or decrease fault levels at th...

Page 4: ...9 78 feet Use 20 AWG wire or larger Control voltage is 120 VAC or 230 VAC or 24 48 VDC or 125 VDC as ordered Check Magnum circuit breaker front cover for Trip Unit Power requirements A remote Stack Light Annunciator Panel or other remote indication device can be connected to remotely verify that the Digitrip is in Maintenance Mode RelayA contact changes state when Digitrip is in Maintenance Mode T...

Page 5: ...Auto OFF max kW max kVA ENABLED DISABLED DT 910 COMM 9600 1200 OPEN TRIP ENABLED DISABLED INCOM ADDRESS INCOM BAUD EXT COMM OpenTrip EXT COMM EXT COMM CLOSE 001 FFE in hex ENABLED DISABLED ENABLED DISABLED NOTE TRIP uses TA device OPEN requires a separate Shunt Trip wired through Aux Relay C terminals A 9 A 10 when programmed as EXT COMM TRIP via PowerNet Requires BC Reset auto in system Appendix ...

Page 6: ... RELAY functions is ENABLED PULSE INITIATE ENABLED PULSE ENABLED kVAh kWh DISABLED RELAY GND TRIP RELAY AmpUNBAL RELAY PH LOSS RELAY OverTEMP RELAY PlugTRIP RELAY CommTRIP ENABLED or DISABLED for all screens RELAY VolUnbal RELAY RevPower RELAY OF TRIP RELAY UF TRIP RELAY OV TRIP RELAY UV TRIP RELAY A GND ALRM RELAY A NeutALRM RELAY A LDPU RELAY A HighLOAD RELAY A OP ALARM RELAY A kW DMND RELAY A P...

Page 7: ...1 XXXX VIEW ADDR 04 XXXXXXXX XXXXXXXX OFF AUX BELL DEAD ALARM WATCH LDT SDT INST GndT GFAlm HLAlm MAINT SEL Each of the 4 addresses is a separate Save group ADDR 01 XXXXXXXX XXXXXXXX XXXXXXXX NO SETTINGS If no relay functions are enabled XXXXXXXX DIGITAL OUTPUT If any relay functions are enabled Save NOTE The MAINT Relay Function will act as an indicator that the Maintenance Mode is enabled and in...

Page 8: ... OUT OF BALANCE 1st Meter screens VOLT UN BALANCE TRIP L L Voltage and FREQ screens displayed See Note 5 PlugTRIP No data displayed 4 If IEC EF style EARTH will replace GROUND UndrVOLT TRIP L L Voltage and FREQ screens displayed See Note 5 RevPower TRIP Power kW screen displayed See Note 5 3 NEUTRAL TRIP is a Long Delay Trip on Neutral or 4th pole NEUTRAL TRIP 1st 2nd Meter screens Note 3 Addition...

Page 9: ...al Auto OFF max kW max kVA ENABLED DISABLED DT 910 COMM 9600 1200 OPEN TRIP ENABLED DISABLED INCOM ADDRESS INCOM BAUD EXT COMM OpenTrip EXT COMM EXT COMM CLOSE 001 FFE in hex ENABLED DISABLED ENABLED DISABLED NOTE TRIP uses TA device OPEN requires a separate Shunt Trip wired through Aux Relay C terminals A 9 A 10 when programmed as EXT COMM TRIP via PowerNet Requires BC Reset auto in system NOTE T...

Page 10: ... NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PUR POSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT INANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON ELECTRI CAL INC THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES IN NO EVE...

Reviews: