I.B. 17555C
Effective November 1999
Page 7
TABLE 2.2 CHARACTERISTIC FOR PHASE ELEMENT
TYPE SETTING
AVAILABLE SETTINGS
TOLERANCE
CURVE #
CURVE SHAPE
IT, I
2
T, I
4
T, FLAT, MOD, VERY, XTRM,
IECA, IECB, IECC, IECD
INVERSE TIME OVERCURRENT
PICKUP
0.20, 0.25, 0.30, 0.35, 0.40, 0.45, 0.50
0.55, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85,
0.90, 0.95,1.00,1.10,1.20,1.30,1.40,
1.50,1.60, 1.70,1.80,1.90,2.00,2.10,
2.20
±5%
INVERSE TIME OVERCURRENT
TIME MULTIPLIER
Curve = IT, I
2
T, I
4
T:
0.20, 0.25, 0.30, 0.35, 0.40, 0.45, 0.50
0.55, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85,
0.90, 0.95, 1.00, 1.25, 1.50, 1.75, 2.00,
2.25, 2.50, 2.75, 3.00, 3.50, 4.00, 4.50,
5.00, 5.50, 6.00, 6.50, 7.00, 7.50, 8.00,
8.50, 9.00, 10.0, 12.5, 15.0, 17.5, 20.0,
22.5, 25.0, 27.5, 30.0, 35.0, 40.0
Curve = FLAT:
0.20, 0.25, 0.30, 0.35, 0.40, 0.45, 0.50,
0.55, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85,
0.90, 0.95, 1.00, 1.25, 1.50, 1.75, 2.00
Curve = ANSI MOD, VERY, XTRM:
0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9,
1.0, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7, 1.8,
1.9, 2.0, 2.1, 2.2, 2.3, 2.4, 2.5, 2.6, 2.7,
2.8, 2.9, 3.0, 3.1, 3.2, 3.3, 3.4, 3.5, 3.6,
3.7, 3.8, 3.9, 4.0, 4.1, 4.2, 4.3, 4.4, 4.5,
4.6, 4.7, 4.8, 4.9, 5.0
Curve = IECA, IECB, IECC, IECD:
0.025, 0.050, 0.075, 0.100, 0.125, 0.150,
0.175, 0.200, 0.225, 0.250, 0.275, 0.300,
0.325, 0.350, 0.375, 0.400, 0.425, 0.450,
0.475, 0.500, 0.525, 0.550, 0.575, 0.600,
0.625, 0.650, 0.675, 0.700, 0.725, 0.750,
0.775, 0.800, 0.825, 0.850, 0.875, 0.900,
0.925, 0.950, 0.975, 1.00
+10%
➀ ➁
± 0.05 SEC
±10%
➀ ➂
±10%
➀ ➂ ➃
IT SC-5392-92B
I
2
T SC-5391-92B
I
4
T SC-5390-92B
FLAT
SC 5393-92B
MOD SC-6685-96
VERY SC-6686-96
XTRM SC-6687-96
IECA SC-6688-96
IECB SC-6689-96
IECC SC-6690-96
IECD SC-6691-96
SHORT DELAY PICKUP
1.00, 1.25, 1.50, 1.75, 2.00, 2.25, 2.50,
2.75, 3.00, 3.50, 4.00, 4.50, 5.00, 5.50,
6.00, 6.50, 7.00, 7.50, 8.00, 8.50, 9.00,
9.50, 10.0, 11.0, NONE
± 10%
SC-5394-92B
SHORT DELAY TIME
(In Seconds)
0.05, 0.10, 0.15, 0.20, 0.25, 0.30, 0.35,
0.40, 0.45, 0.50, 0.55, 0.60, 0.65, 0.70,
0.75, 0.80, 0.85, 0.90, 0.95,1.00,1.25,
1.50
± 0.05 SEC
SC-5394-92B
INSTANTANEOUS PICKUP
1.00, 1.25, 1.50, 1.75, 2.00, 2.25, 2.50,
2.75, 3.00, 3.50, 4.00, 4.50, 5.00, 5.50,
6.00, 6.50, 7.00, 7.50, 8.00, 8.50, 9.00,
9.50, 10.0, 12.5, 15.0, 17.5, 20.0, 22.5,
25.0, NONE
± 10%
SC-5396-92B
DISCRIMINATOR
(If Phase INST set to NONE)
D ON Fixed At 11 x I
n
D OFF
+10%
NOTES:
➀
Curves go to constant operating time above 30 X I
n
.
➁
Tolerance: ± 10% or 0.09 seconds, whichever is larger. Minimum operating trip time is 0.05 seconds.
➂
Tolerance: ± 10% or 0.09 seconds, whichever is larger (>1.5 x I
pu
). Minimum trip time is 2 power line cycles.
➃
For IECD, the Time Multiplier Tolerance is ±0.05 seconds.
Summary of Contents for Cutler-Hammer Digitrip 3000
Page 18: ...I B 17555C Effective November 1999 Page 12 Fig 2 1 Typical Communications Wiring Diagram...
Page 27: ...I B 17555C Effective November 1999 Page 21 Fig 3 1 Digitrip 3000 Typical Wiring Diagram...
Page 36: ...I B 17555C Effective November 1999 Page 30 Fig 3 11 Local Programming Sequence Flow Chart...
Page 37: ...I B 17555C Effective November 1999 Page 31...
Page 52: ...I B 17555C Effective November 1999 Page 46 Fig 7 5 Short Delay Phase Curves SC 5394 92B...
Page 54: ...I B 17555C Effective November 1999 Page 48 Fig 7 7 Instantaneous Curves SC 5396 92B...
Page 59: ...I B 17555C Effective November 1999 Page 53 Fig 7 12 Short Delay Ground Curves SC 5403 92B...
Page 60: ...I B 17555C Effective November 1999 Page 54 Fig 7 13 ANSI Moderately Inverse Curves SC 6685 96...
Page 61: ...I B 17555C Effective November 1999 Page 55 Fig 7 14 ANSI Very Inverse Curves SC 6686 96...
Page 62: ...I B 17555C Effective November 1999 Page 56 Fig 7 15 ANSI Extremely Inverse Curves SC 6687 96...
Page 63: ...I B 17555C Effective November 1999 Page 57 Fig 7 16 IEC A Moderately Inverse Curves SC 6688 96...
Page 64: ...I B 17555C Effective November 1999 Page 58 Fig 7 17 IEC B Very Inverse Curves SC 6689 96...
Page 65: ...I B 17555C Effective November 1999 Page 59 Fig 7 18 IEC C Extremely Inverse Curves SC 6690 96...
Page 66: ...I B 17555C Effective November 1999 Page 60 Fig 7 19 IEC D Flat Curves SC 6691 96...
Page 68: ...I B 17555C Effective November 1999 Page 62...
Page 73: ...I B 17555C Effective November 1999 Page A5 Fig A 7 DT3001 Typical Wiring Diagram...
Page 76: ...I B 17555C Effective November 1999 Page A8...
Page 81: ...I B 17555C Effective November 1999 Page B5 Fig B 2 Digitrip 3010 3020 Dimensions Inches...
Page 83: ...I B 17555C Effective November 1999 Page B7 Fig B 3 Digitrip 3010 3020 Typical Wiring Diagram...
Page 89: ...I B 17555C Effective November 1999 Page B13...
Page 90: ...I B 17555C Effective November 1999 Page B14...