DT3000 AND DT3030 SPECIFICATIONS AND TEST SUMMARY
COMPLIANCE TESTING:
Certifications:
•
UL Recognized, File # E154862
•
UL 1053 (1994)
•
ANSI C37.90 (1989)
•
EN 61010-1 (1993) - DT3030 Model Only
•
EN 55011 (1991)
•
CE Compliant - DT3030 Model Only
Emission Tests:
•
EN 55011 (1991) - Group 1 Class A
•
FCC 47 CFR Chapter 1 - Part 15 Subpart b Class A
Immunity Tests:
•
ANSI C37.90.1 (1989) - Surge Withstand Capability
•
ANSI C37.90.2 (1995) - EMI Immunity to 35V/m
•
EN 61000-4-2 (1995) - ESD Rating of 8kV
•
IEC 255-22-2 (1989) - ESD Rating of 8kV
•
EN 61000-4-3 (1997) - Radiated EM Field at 10V/m
•
IEC 255-22-3 (1989) - Radiated EM Field at 10V/m
•
IEC 801-3 (1984) - Radiated EM Field at 10V/m
•
EN 61000-4-4 (1995) - Fast Transient Burst at 2kV
•
IEC 255-22-4 (1992) - Fast Transient Burst at 2kV
•
EN 61000-4-6 (1996) - Conducted RF at 10Vo
CURRENT INPUTS:
•
Cts:
5A Secondary
•
Ct Burden:
<0.004 ohm
<0.1 VA @ Rated Current (5A)
•
I
n
:
5A (Secondary or CT (Primary)
•
Saturation:
30 x I
n
•
Ct Thermal Rating:
10A continuous
500A for 1 Second
CT (PRIMARY) SETTING AVAILABLE:
•
Phase & Ground
10/25/50/75/100/150/200/250/300/
400/500/600/630/800/1000/1200/
1250/1500/1600/2000/2400/2500/
3000/3200/4000/5000
CURRENT MONITORING:
•
True RMS Sensing:
3-Phase and Ground
•
Display Accuracy:
±1% of Full Scale [I
n
] from
0.04xIn to 1xI
n
±2% of Full Scale [I
n
] from 1xI
n
to 2xI
n
•
Amp Demand:
Average demand over 5
minute sampling window
•
High Load Threshold:
85% of Long Delay or Inverse
Time Overcurrent Setting
OUTPUT TRIP CONTACTS:
(Trip OC/Comm, Trip Inst, & Comm Close)
•
Momentary:
Make 30A ac/dc for 0.25 sec
Break 0.25A @ 250Vdc
Break 5A @ 120/240Vac
•
Continuous:
5A @ 120/240Vac
5A @ 30Vdc
•
Meets ANSI C37.90, paragraph 6.7
CONTROL POWER:
•
Input Voltage:
Nominal
Oper. Range
DT3000
48 to 250Vdc
28 to 280Vdc
120 to 240Vac
90 to 254Vac
(50/60Hz)
(50/60Hz)
DT3030:
24 to 48 Vdc
19 to 56Vdc
•
Power Consumption:
DT3000
DT3030:
10VA maximum
PHASE AND GROUND TIME-CURRENT CURVES:
•
Thermal
It
[Moderately Inverse]
I
2
t
[Very Inverse]
I
4
t
[Extremely Inverse]
Flat
[Definite Time]
•
ANSI:
Moderately Inverse
(Per ANSI C37.112, 1996)
Very Inverse
Extremely Inverse
•
IEC:
IEC-A
[Moderately Inverse]
(Per IEC 255-3, 1989)
IEC-B
[Very Inverse]
IEC-C
[Extremely Inverse]
IEC-D
[Definite Time]
PHASE OVERCURRENT PICKUP RANGES:
•
Inverse Time Overcurrent
Setting:
(0.2 to 2.2) x I
n
[29 settings]
•
Short Delay Setting:
(1 to 11) x I
n
, None [25 settings]
•
Instantaneous Setting: (1 x 25) x I
n
, None [30 settings]
GROUND OVERCURRENT PICKUP RANGES:
•
Inverse Time Overcurrent
Setting:
(0.1 to 2.0) in I
n
[26 settings]
•
Short Delay Setting:
(0.1 to 11 x I
n
, None [45 settings]
•
Instantaneous Setting: (0.5 to 11 x I
n
, None [33 settings]
TIME DELAY SETTINGS:
•
Inverse Time Overcurrent
Time Multiplier:
It, I2t, I4t Curve: 0.2 to 40 [48 settings]
Flat: 0.2 to 2.0 [21 settings]
ANSI (all): 0.1 to 5.0 [50 settings]
IEC (all): 0.025 to 1.00 [40 settings]
•
Short Delay Time:
0.05 to 1.5 sec. [22 settings]
TIMING ACCURACY:
•
Inverse Time Overcurrent Time: ±10% @ >1.5 x Pickup
•
Short Delay Time:
±50ms
48
Vdc
125
Vdc
250
Vdc
120
Vac
240
Vac
10VA
10VA
10VA
10VA
18VA
Summary of Contents for Cutler-Hammer Digitrip 3000
Page 18: ...I B 17555C Effective November 1999 Page 12 Fig 2 1 Typical Communications Wiring Diagram...
Page 27: ...I B 17555C Effective November 1999 Page 21 Fig 3 1 Digitrip 3000 Typical Wiring Diagram...
Page 36: ...I B 17555C Effective November 1999 Page 30 Fig 3 11 Local Programming Sequence Flow Chart...
Page 37: ...I B 17555C Effective November 1999 Page 31...
Page 52: ...I B 17555C Effective November 1999 Page 46 Fig 7 5 Short Delay Phase Curves SC 5394 92B...
Page 54: ...I B 17555C Effective November 1999 Page 48 Fig 7 7 Instantaneous Curves SC 5396 92B...
Page 59: ...I B 17555C Effective November 1999 Page 53 Fig 7 12 Short Delay Ground Curves SC 5403 92B...
Page 60: ...I B 17555C Effective November 1999 Page 54 Fig 7 13 ANSI Moderately Inverse Curves SC 6685 96...
Page 61: ...I B 17555C Effective November 1999 Page 55 Fig 7 14 ANSI Very Inverse Curves SC 6686 96...
Page 62: ...I B 17555C Effective November 1999 Page 56 Fig 7 15 ANSI Extremely Inverse Curves SC 6687 96...
Page 63: ...I B 17555C Effective November 1999 Page 57 Fig 7 16 IEC A Moderately Inverse Curves SC 6688 96...
Page 64: ...I B 17555C Effective November 1999 Page 58 Fig 7 17 IEC B Very Inverse Curves SC 6689 96...
Page 65: ...I B 17555C Effective November 1999 Page 59 Fig 7 18 IEC C Extremely Inverse Curves SC 6690 96...
Page 66: ...I B 17555C Effective November 1999 Page 60 Fig 7 19 IEC D Flat Curves SC 6691 96...
Page 68: ...I B 17555C Effective November 1999 Page 62...
Page 73: ...I B 17555C Effective November 1999 Page A5 Fig A 7 DT3001 Typical Wiring Diagram...
Page 76: ...I B 17555C Effective November 1999 Page A8...
Page 81: ...I B 17555C Effective November 1999 Page B5 Fig B 2 Digitrip 3010 3020 Dimensions Inches...
Page 83: ...I B 17555C Effective November 1999 Page B7 Fig B 3 Digitrip 3010 3020 Typical Wiring Diagram...
Page 89: ...I B 17555C Effective November 1999 Page B13...
Page 90: ...I B 17555C Effective November 1999 Page B14...