I.B. 17555C
Effective November 1999
Page 39
TABLE 6.1 TROUBLESHOOTING GUIDE
Symptom
Probable Cause
Possible Solution(s)
Reference
Operational LED is Off
Protective Relay’s Control
Power is Deficient or Absent
Protective Relay is
Malfunctioning
Verify that Control Power is Connected
Between TB1 -5 and TB1 -6 and that it
is within Specifications
Replace the Protective Relay
Figure 3-1 and
Paragraph 2-3
Paragraph 6-3
Operational LED is On
but Does not Blink
Protective Relay’s Control
Power is Deficient or Absent
Protective Relay is
Malfunctioning
Verify that Control Power is Connected
Between TBI-5 and TBI-6 and it is
within Specifications
Replace the Protective Relay
Figure 3-1 and
Paragraph 2-3
Paragraph 6-3
Operational LED
Blinks Red or is any
Color other than a
Definite Red or Green
Internal Problem
Detected
Press Reset Pushbutton
Reprogram Setpoints
Replace Protective Relay if Symptom
Persists
Paragraph 2-2.1
and 3-2
Paragraph 3-3.2
Paragraph 6-3
“PGRM” Appears in
Settings Display Window
Setpoints are Invalid
Check sum did not Match
Reprogram Setpoints
Replace Protective Relay if “PGRM”
Reappears After Saving Settings
Paragraph 3-3.2
Paragraph 6-3
“ERR” Appears in Setting There was an Error During
Setpoint Programming
There was an Error While
in the Test Mode
Make Sure DIP switch S2 is in
Correct Position
More than 0.1 Per Unit of Current
Cannot Flow While in Test Mode
Table 5.1
Paragraph 3-3.3
“RAM” Appears in
Settings Display Window
An Internal RAM Check
Failed
Remove Power from the Protective
Relay and then Reapply Power - If the
Symptom Persists, Replace the
Protective Relay
Paragraph 6-3
Current Readings Appear
Incorrect
Incorrect CT Ratio used
in Equipment
Incorrect Current Wiring
Verify CT Ratio in Equipment
Verify Connections on CT Wiring
Paragraph 1-3
and Paragraph 3-3.2
Figure 3-1
Current Readings
Appear Incorrect
Incorrect System Frequency
Programmed
Breaker “b” Contact to trip
unit not functioning
Set to Correct Frequency
Insure “b” Contact Type is Connected
to Protective Relay and Functioning
Paragraph 3-3.2
Figure 3-1
Circuit Breaker Trips
Much Faster than
Expected on Inverse
Time Overcurrent
Incorrect Settings
Phase Zone Interlocking not
used and Jumper Missing
Ground Zone Interlocking not
Used and Jumper Missing
Zone Interlocking Used
Check Settings
Check for Phase Zone Interlocking
Jumper Between TB1 -13 and TB1 -14
Check for Ground Zone Interlocking
Jumper Between TB1 -11 and TB1 -12
Check for Absence of Blocking
Signal from “Down-Stream” Breaker
NOTE:
During an Internal Test, there is
No Blocking Signal from a
“DownStream” Breaker, there-
fore, add jumper for test.
Paragraph 3-3.2 and
Table 5.1
Figure 3-1
Figure 3-1
Paragraph 4-2
Summary of Contents for Cutler-Hammer Digitrip 3000
Page 18: ...I B 17555C Effective November 1999 Page 12 Fig 2 1 Typical Communications Wiring Diagram...
Page 27: ...I B 17555C Effective November 1999 Page 21 Fig 3 1 Digitrip 3000 Typical Wiring Diagram...
Page 36: ...I B 17555C Effective November 1999 Page 30 Fig 3 11 Local Programming Sequence Flow Chart...
Page 37: ...I B 17555C Effective November 1999 Page 31...
Page 52: ...I B 17555C Effective November 1999 Page 46 Fig 7 5 Short Delay Phase Curves SC 5394 92B...
Page 54: ...I B 17555C Effective November 1999 Page 48 Fig 7 7 Instantaneous Curves SC 5396 92B...
Page 59: ...I B 17555C Effective November 1999 Page 53 Fig 7 12 Short Delay Ground Curves SC 5403 92B...
Page 60: ...I B 17555C Effective November 1999 Page 54 Fig 7 13 ANSI Moderately Inverse Curves SC 6685 96...
Page 61: ...I B 17555C Effective November 1999 Page 55 Fig 7 14 ANSI Very Inverse Curves SC 6686 96...
Page 62: ...I B 17555C Effective November 1999 Page 56 Fig 7 15 ANSI Extremely Inverse Curves SC 6687 96...
Page 63: ...I B 17555C Effective November 1999 Page 57 Fig 7 16 IEC A Moderately Inverse Curves SC 6688 96...
Page 64: ...I B 17555C Effective November 1999 Page 58 Fig 7 17 IEC B Very Inverse Curves SC 6689 96...
Page 65: ...I B 17555C Effective November 1999 Page 59 Fig 7 18 IEC C Extremely Inverse Curves SC 6690 96...
Page 66: ...I B 17555C Effective November 1999 Page 60 Fig 7 19 IEC D Flat Curves SC 6691 96...
Page 68: ...I B 17555C Effective November 1999 Page 62...
Page 73: ...I B 17555C Effective November 1999 Page A5 Fig A 7 DT3001 Typical Wiring Diagram...
Page 76: ...I B 17555C Effective November 1999 Page A8...
Page 81: ...I B 17555C Effective November 1999 Page B5 Fig B 2 Digitrip 3010 3020 Dimensions Inches...
Page 83: ...I B 17555C Effective November 1999 Page B7 Fig B 3 Digitrip 3010 3020 Typical Wiring Diagram...
Page 89: ...I B 17555C Effective November 1999 Page B13...
Page 90: ...I B 17555C Effective November 1999 Page B14...