Effective Date: 12/05
For more information visit:
www.eatonelectrical.com
Page 9-7
FP-5000
IL17569B
Page 9-7
Effective Date: 12/05
Table 9.6 Control Option Definitions
Control Option
Description
Open Bkr
A command to open breaker
Close Bkr
A command to close breaker
Open
A flag to indicate that breaker is open
Closed
A flag to indicate the the breaker is closed
BkFailAlm
Breaker failure alarm flag
StateAlm
Breaker status disagreeement alarm
Mntr1Alm
Trip coil broken alarm
Mntr2Alm
Close coil broken alarm
AllAlm
All alarm flag
67G-F
Ground fault direction: Forward
67G-R
Ground fault direction: Reverse
67V-F
Zero sequence voltage polarized fault direction: Forward
67V-R
Zero sequence voltage polarized fault direction: Reverse
67Q-F
Negative sequence voltage polarized fault direction: Forward
67Q-R
Negative sequence voltage polarized fault direction: Reverse
67I-F
Neutral current polarized fault direction: Forward
67I-R
Neutral current polarized fault direction: Reverse
67X-F
Fourth CT fault current direction: Forward
67X-R
Fourth CT fault current direction: Reverse
67X-F
Fourth CT fault current direction: Forward
67VIXF
Fourth CT Zero sequence voltage polarized fault current direction: Forward
67VIXR
Fourth CT Zero sequence voltage polarized fault current direction: Reverse
67A-F
Phase A current direction: Forward
67B-F
Phase B current direction: Forward
67C-F
Phase C current direction: Forward
SynchFail
Synch fail alarm
SlipAlm
Frequency difference between tow voltage sources is out of range
25BL
Bus voltage normal
25LL
Line voltage normal
ColdLoad
In cold load condition (load is energized after a specified time of outage with inrush current)