Effective Date: 12/05
For more information visit:
www.eatonelectrical.com
Page 12-9
FP-5000
IL17569B
Page 12-9
Effective Date: 12/05
All contact output changes will be logged in the event log and no programming is necessary. If more than one relay changes state at exactly
the same time because of a single causal event activating more than one relay, only one log is entered into the event log. Table 12.8
summarizes all output event causes that will be logged.
Table 12.8 Event Output Cause Table
Cause
Cause Description
Value Given
Relay Changed
One of the first 6 relays – Trip 1, Trip 2,
Output Status – contains the status flag for
Rly3, Rly4, Rly5, or Alarm – has changed state
all contact outputs
Healthy State
The Relay Healthy contact output
Output Status – contains the status flag for
has changed state
all contact outputs
Breaker commands that come through the FP-5000, breaker state changes and breaker alarms are all logged automatically in the event log.
Table 12.9 shows all possible causes for breaker event logs.
Table 12.9 Event Breaker Cause Table
Cause
Cause Description
Value Given
Open Breaker
An Open Breaker command is given
Breaker Status – contains all the flags
remotely or through the front panel pushbutton
related to the breaker
Close Breaker
A Close Breaker command is given remotely
Breaker Status – contains all the flags
or through the front panel pushbutton
related to the breaker
Bkr Opened
The Breaker State is determined to be Opened
Breaker Status – contains all the flags
related to the breaker
Bkr Closed
The Breaker State is determined to be Closed
Breaker Status – contains all the flags
related to the breaker
Bkr Lockout
The Breaker has failed to break the current
Breaker Status – contains all the flags
in the programmed amount of time
related to the breaker
Slow Bkr Alm
The Breaker has taken more than 40 cycles
Breaker Status – contains all the flags
to close or more than 30 cycles to open
related to the breaker
Bkr State Alm
There is a state disagreement between
Breaker Status – contains all the flags
the 52A and 52B contact inputs.
related to the breaker
Trip1 Mntr Alm
The Breaker is determined to be in the closed
Breaker Status – contains all the flags
state and no trickle open (trip) coil current
related to the breaker
is sensed around the Trip 1 contact output
Trip2 Mntr Alm
The Breaker is determined to be in the open
Breaker Status – contains all the flags
state and no trickle close coil current is
related to the breaker
sensed around the Trip 2 contact output
Whenever the communication variable input changes, if so programmed, it will be logged in the event log.
Table 12.10 shows the cause for this event log.
Table 12.10 Event Communication Cause Table
Cause
Cause Description
Value Given
CommLogic Alt
Communication Logic variable has
Communication Logic Status – contains all
changed state
4 communication logic variable states