13.5 Standards Compliance
The following table shows the standards to which the FP-5000 complies and, where appropriate, the rating achieved under the standard’s
categories. Note that, in most cases, the performance levels exceed the levels given. This table is not a maximum performance specification,
rather it shows compliance to published numbers in the standards.
NORTH AMERICAN STANDARDS
ANSI/IEEE
ANSI/IEEE C37.90-1989
Performance Standard for Relay Systems associated with
electric power apparatus
ANSI C37.90.1 (1989) Surge Withstand Capability
Oscillatory Surge Wave Compliance (OSWC)
2.5 kV
Fast Transient Surge Wave Compliance (FTSWC)
4.0 kV
ANSI C37.90.2 (1995) RF radiated immunity
RF Radiation Withstand
to > 35 V/M; 27 - 1000 MHz
UL/CUL
FP-5000 UL Compliance is covered under UL File Number E154862
Catalog # FP-5000-00 5 Amp Version only, FP5100-00 1 Amp version pending
UL-1053
Ground Fault Interruption (GFI) for Protective Relaying (PR) Equipment Performance - FP-5000-00 5 Amp
version only, FP-5100-00 1 Amp version pending
UL-508
Spacing of conductors, Safety, Fire
FCC
CFR 47 FCC Part 15 Subpart b Class A
EMF radiation limitation
EUROPEAN STANDARDS
Emissions
EN-50081-2
EN 50011 CISPR-11, Class A
Immunity EN-61000-6-2 (1999)
IEC 61000-4-2 ESD Immunity
Electrostatic discharge, 8/6 kV; Air/Contact
IEC 61000-4-3 RF Radiated Immunity
RF Radiation, 10 V/M 80-1000 MHz (1kHz 80% Amplitude Modulation)
IEC 61000-4-4 EFT/Burst Immunity
Electrical Fast Transient, 4/2 kV; CM/DM
IEC 61000-4-5 Surge Immunity
Surge, 2/1kV; CM/DM
IEC 61000-4-6 RF Conducted Immunity
RF Conductive, 10 Vo; 0.150-80 MHz
IEC 61000-4-8 Power Frequency
Magnetic Field, 50/60 Hz 30 A/m
Magnetic Field Immunity
IEC 61000-4-11 Voltage Variation Immunity test
Voltage dips, 30% reduction, 0.5 periods; 60% reduction 5/50 periods.
Voltage Interruption 95% reduction 250 periods