FP-5000
IL17569C
Page 3-1
Effective Date: 12/05
Effective Date: 12/05
For more information visit:
www.eatonelectrical.com
Page 3-1
3
SPECIFICATIONS
3.1 Table of Specifications
Note that accuracy specifications for the FP-5000 are for operation within the nominal frequency range of 50 Hz or 60 Hz at + 5 Hz.
Unless stated otherwise, Operating Power Factors “0.50 Lagging” to “Unity” to “0.50 Leading.”
Control Power:
TB101-102 (101 positive for dc)
Standard Power Supply Board
250V Power Supply Board
ac Nominal Voltage
100 – 120 Vac
100-240 Vac
ac Excursion Range
55 – 132 Vac
55 - 264 Vac
ac Frequency Range
50/60 Hz nom. + 5%
50/60 Hz nom. + 5%
dc Nominal Voltage
48 – 125 Vdc
100 - 250 Vdc
dc Excursion Range
38 – 150 Vdc
80 - 300 Vdc
Interruption ride through time
83ms for 120V, 60 Hz ac
250ms for 110 Vdc
300ms for 110 Vac
Power Consumption 20 VA max.
20 VA
22 VA
Current Transformer Inputs:
TB4 A, B, C, X
FP-5000-00
FP-5100-00
Nominal (I
nom
):
5 A
1 A
CT Rating: Steady state
2 x I
nom
= 10 A
3 x I
nom
= 3 A
maximum transient
80 x I
nom
= 400 A for 1 sec.
100 x I
nom
= 100 A for 1 sec.
CT Burdens
< 0.25 VA @ 5 A (Nominal)
< 0.05 VA @ 1 A (Nominal)
Contact Inputs:
TB201-204, 206-209, Source TB205, 210
Number of contact inputs
Cin1 – Cin8
Rating
40 Vdc @ 2 mA/C In draw wetting voltage provided
with internal return only
Voltage Transformer Inputs:
TB213-217, VA, VB, VC, VX1, VX2
Nominal
0 – 120 Vac Line to common
Operating Range
0 – 144 Vac (+20%) Line to common
Internal Burden Loading
1 Meg Input Impedance
Reference
TB218, Vg internal 120 ohm PTC to chassis ground
Relay Output:
TB103-118
Number & type of output contacts
2 Form C, NO & NC TB103-105, 106-108
5 Form A, NO only
TB109/110, 111/112, 113/114, 115/116, 117/118