Effective Date: 12/05
For more information visit:
www.eatonelectrical.com
Page 5-5
FP-5000
IL17569C
Page 5-5
Effective Date: 12/05
Table 5.2 Protection
Display Setting
Description
Setpoint Range/
Value Selection
Default
Setting
Selected
Value
Refer to
Sec. #
51P-1 PH TOC
Curve
Phase Time Overcurrent Curve
Element #1 Settings
Shape:
Select curve characteristic shape
IT, I2T, I4T, FLAT, MOD,
VERY, XTRM, IECA, IECB,
IECC
MOD
Reset:
Select curve reset characteristics
Inst, Calc, T Delay
Calc
Direction:
Select direction
Forward, Reverse, Both
Both
51P-1 PH TOC
Setting
Phase Time Overcurrent Pickup and
Time Multiplier Element #1 Settings
Pickup:
Select current pickup value in per
unit values (x I
nom
)
0.1 to 4.0
pu
or Disable
(0.01 increments)
1.00
Time Mult:
Select Time Multiplier
0.05 to 10.0
(.01 increments)
1.00
Vrestraint
Reserved for later use
60 to 150 Volts or Disable
(Increments of 1)
(151=disable)
Disable
51P-2 PH TOC
Curve
Phase Time Overcurrent Curve
Element #2 Settings
Shape:
Select curve characteristic shape
IT, I2T, I4T, FLAT, MOD,
VERY, XTRM, IECA, IECB,
IECC
MOD
Reset:
Select curve reset characteristics
Inst, Calc, T Delay
Calc
Direction:
Select direction
Forward, Reverse, Both
Both
51P-2 PH TOC
Setting Pickup
Phase Time Overcurrent Pickup and
Time Multiplier Element #2 Settings
Pickup:
Select current pickup value in per
unit values (x I
nom
)
0.1 to 4.0
pu
or Disable
(0.01 increments)
1.00
Time Mult:
Select Time Multiplier
0.05 to 10.0
(.01 increments)
2.00
Vrestraint
Select the maximum secondary
voltgage restraint level
60 to 150 Volts or Disable
(Increments of 1)
(151=disable)
Disable
50P-1 PH IOC 1
Phase Overcurrent Element #1
Setting
Pickup:
Select current pickup value in per
unit values (x I
nom
)
0.1 to 20.0
pu
or Disable
(0.01 increments)
2.00
Delay (c):
Select delay time in cycles
0 to 9999 cycles
(1 cycle increments)
0
Direction:
Select direction
Forward, Reverse, Both
Both
Setting Group ______
Phase Overcurrent : Phase time overcurrent (51P-1 & 51P-2) and instantaneous (50P-1 & 50P-2) protective device
settings
5.5.2.1
8.3
13.4
5.5.2.1
8.3
5.5.2.1
8.3
13.4
5.5.2.1
8.3
5.5.2.1
8.3