FP-5000
IL17569C
Page 5-9
Effective Date: 12/05
Display Setting
Description
Setpoint Range/
Value Selection
Default
Setting
Selected
Value
Refer to
Sec. #
59N-1 OV
Definition
Neutral Overvoltage Settings
Source:
Select if the operation is based on
calculated or measured voltgage
Calculated, measured
(0=calculated, 1=measured)
Calculated
Criterion:
Select if the threshold is based on
fundamental or rms
Phasor, RMS
(0=Phasor, 1=RMS)
Phasor
59N-1 OV Trip
Neutral Overvoltage Trip Settings
Threshold:
Select magnitude of overvoltage
required
5 to 250 Volts
(Increments of 1)
(251=disable)
Disable
Delay (c):
Select delay time in cycles
0 to 9999 cycles
(1 cycle increments)
1200
Neutral V Protection:
Select neutral voltage device settings
5.5.2.5
8.6.2
5.5.2.5
8.6.2
Display Setting
Description
Setpoint Range/
Value Selection
Default
Setting
Selected
Value
Refer to
Sec. #
27A-1
Undervoltage
Auxiliary VT Undervoltage Settings
Threshold:
Select magnitude of undervoltage
required
10 to 250 Volts, disable
(1 Volt increments)
Disable
Delay (c):
Select delay time in cycles
0 to 9999 cycles
(1 cycle increments)
1200.00
59A-1
Overvoltage
Auxiliary VT Overvoltage Settings
Threshold:
Select magnitude of overvoltage
required
10 to 250 Volts, disable
(1 Volt increments)
Disable
Delay (c):
Select delay time in cycles
0 to 9999 cycles
(1 cycle increments)
1200
Aux V Protection:
Select undervoltage (27A-1) and overvoltge (59A-1) device settings
5.5.2.5
8.6.2
5.5.2.5
8.6.2