Page 5-17
FP-5000
IL17569C
Page 5-17
Effective Date: 12/05
System Alarms (continued)
Display Setting
Description
Setpoint Range/
Default
Selected
Refer to
Value Selection
Setting
Value
Sec. #
VA Demand
System VA Demand
5.5.3
Alarm
Alarm Setting
Units:
Select units for VA demand
kVA or MVA
kVA
Threshold:
Select magnitude threshold
1 to 40,000, Disable
Disable
in primary units
(increments of 1)
Delay (m):
Select delay time in minutes
0 to 60 minutes
0
(increments of 1)
Current Demand
System Current Demand
5.5.3
Alarm
Alarm Setting
Pickup:
Select pickup in primary units
10 to 10,000 amps,
Disable
Disable (increments of 10)
Delay (m):
Select delay time in minutes
0 to 60 minutes
0
(increments of 1)
I THD Alarm
System Current Total Harmonic
5.5.3
Distortion Alarm Setting
Threshold:
Select magnitude of I THD
(Phase CT Primary/100) to
Disable
in primary units
(Phase CT Primary *10)
[increments of Phase CT
Primary/100]
Delay (m):
Select delay time in minutes
0 to 3600 seconds
0
(increments of 1s)
V THD Alarm
System Voltage Total Harmonic
5.5.3
Distortion Alarm Setting
Threshold:
Select magnitude of V THD
Main VTR/10 to
Disable
in primary units
Main VTR *10
(increments of
Main VTR/100)
Delay (m):
Select delay time in minutes
0 to 3600 seconds
0
(increments of 1s)
Breaker Alarm
Breaker alarm # of operations
5.5.3
& sum of interrupting amps
# of Operation:
# of breaker operations based
1 to 9999
9999
on the 52a and 52b contacts
(increments of 1)
Isum INTR Amp:
Current sum of interrupting
0 to 50,000 kA
2
seconds
50,000
amps measured in kA
2
(increments of 1 kA
2
s)