IL17569C
Page 5-34
FP-5000
Effective Date: 12/05
Page 5-34
For more information visit:
www.eatonelectrical.com
Effective Date: 12/05
Display Setting
Description
Setpoint Range/
Value Selection
Default
Setting
Selected
Value
Refer to
Sec. #
Block 51X TOC
Logic gate setting to block 51X TOC
operation
Function:
Select logic function to apply to logic
gate
OR, AND, NOR, NAND,
disable
Disable
Set Group:
Select protection setting group for
logic gate to apply
1, 2, 3, 4 or All
1
IN1:
Select logic type for logic input 1
*See Logic Input Options
Table 5.10
Unused
IN2:
Select logic type for logic input 2
*See Logic Input Options
Table 5.10
Unused
IN3:
Select logic type for logic input 3
*See Logic Input Options
Table 5.10
Unused
IN4:
Select logic type for logic input 4
*See Logic Input Options
Table 5.10
Unused
Logic Latch 1
Logic Latch 1 Settings
Set Group:
Select protection setting group for
logic latch to apply
1, 2, 3, 4 or All
1
Sin:
Select logic input to set latch
*See Logic Input Options
Table 5.10
Unused
Rin:
Select logic input to reset latch
*See Logic Input Options
Table 5.10
Unused
Logic Latch 2
Logic Latch 2 Settings
Set Group:
Select protection setting group for
logic latch to apply
1, 2, 3, 4 or All
1
Sin:
Select logic input to set latch
*See Logic Input Options
Table 5.10
Unused
Rin:
Select logic input to reset latch
*See Logic Input Options
Table 5.10
Unused
Programmable Logic:
cont.
5.5.7
9.3
9.6
5.5.7
9.3
9.6
5.5.7
9.3
9.6