Page 7-1
IL17569
Effective June, 2001
7 STARTUP
General
— This section lists the procedure for applying power to an
FP-5000 for the first time. Use it as a checklist to reduce the chance
of skipping an item.
DANGER
ONLY QUALIFIED PERSONNEL FAMILIAR WITH THE FP-5000,
THE BREAKER, AND ITS ASSOCIATED MECHANICAL EQUIP-
MENT, SHOULD PERFORM THESE STARTUP PROCEDURES.
FAILURE TO COMPLY CAN RESULT IN SERIOUS OR FATAL
INJURY AND/OR EQUIPMENT DAMAGE.
CAUTION
NEVER HIGH POT THE FP-5000 CIRCUITS BEYOND
1500VRMS/1 MIN. DO NOT USE A MEGGER
®
, HI-POT, OR
OTHER HIGH VOLTAGE INSULATION TESTER ON THE FP-5000
TERMINALS, IT HAS BEEN FACTORY TESTED, AND FIELD
TESTING MAY CAUSE UNNECESSARY STRESS. REMOVE THE
FP-5000 INNER CHASSIS WHEN TESTING THE PROTECTIVE
RELAY SYSTEM.
CAUTION
DO NOT USE A MEGGER
®
, HI-POT, OR OTHERWISE HIGH
VOLTAGE TO TEST THE FOLLOWING TERMINALS OR POINTS:
• TB3 - J1-3 SHIELD – IS BONDED TO HOUSING
(FILTER CLAMP)
• TB3 - J2-3 SHIELD – IS BONDED TO HOUSING
(FILTER CLAMP)
• TB3 - J3-5 SHIELD – IS BONDED TO HOUSING
(DIRECT GROUND)
• TB2 - 218 VG (REF.) – IS BONDED TO HOUSING
(FILTER CLAMP)
• FRONT RS-232 PROGRAMMING PORT SHELL – IS BONDED
TO HOUSING (DIRECT GROUND)
Startup consists of Programming the necessary operational
parameters, verifying the operation of the FP-5000, checking the
wiring, and verifying the reasonable operation of the system
components before attempting to place the equipment into
continuous service.
The programming should already be done before FP-5000 is placed
into service. Protection parameters may be reviewed in the View
Settings mode or adjusted in the Set Mode.
Refer to wiring
Figures 2-2
and
2-3
and
Figure 6-5
on terminal
definitions, Section 3 “Specifications” for nominal ratings during
startup.
7.1 Power-Off Checks
With the incoming AC distribution power locked off and after all
sources of power to the FP-5000 are de-energized, including control
system battery, check the wiring for conformance to the wiring plan
developed for the application.
• Verify that the Ct secondary current rating and the FP-5000 Ct
input rating style agree (either 5A or 1A). See Section 1.8
Ordering Information for catalog number identification.
• Verify that the Voltage Inputs are referenced to Voltage transform-
ers where the common is earth ground. TB2 Terminal 218 “Vg” is
internally bonded within the FP-5000 to protective earth and can
not be connected to neutral or a phase reference.
WARNING
VOLTAGE TRANSFORMERS ARE OFTEN CONNECTED
“UPSTREAM” FROM THE BREAKER CIRCUIT MONITORED
AND SO MAY BE DIFFICULT TO DISENGAGE.
7.2 Initial Control Power-On Checks
• All power sources should be disconnected as described in Section
7.1.
• Disable all trip and control circuits.
• Disconnect and insulate the breaker trip coil load leads from any
of the trip relay terminals, typically Relay1 and Relay2 on TB1
terminals 116 and 118, to prevent breaker from energizing during
most of this testing.
• Disconnect and insulate any control circuit loads connected to the
remaining control relays on the FP-5000.
• Verify FP-5000 power supply control power:
– Disconnect the AC or DC control power lead to terminals
TB101(+).
– Connect a voltmeter to the circuit that fed TB101 and the
return on TB102.
– Energize the FP-5000 power supply power source
and monitor the voltage.
– Make sure that it is within nominal specifications:
– Battery system 48 – 125V DC or
control power transformer 100 – 120V AC.
– De-energize the power supply source.
• Verify trip relay control voltage:
– Connect a voltmeter between each trip relay breaker trip coil
load wire just disconnected from terminal 116 or 118, and the
other meter lead to the control power source (TB115/117).
– Energize the trip coil source power.
– Measure the voltage and ensure that it is within the FP-5000
trip relay nominal specifications.
– De-energize the control power and troubleshoot
as necessary.
• Verify the FP-5000 Relay Health Alarm, Breaker Alarm and
any other auxiliary FP-5000 relay control circuit in the same
manner as the trip relay circuits.
Summary of Contents for Cutler-Hammer FP-5000
Page 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay...
Page 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally...
Page 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application...
Page 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application...
Page 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally...
Page 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally...
Page 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally...
Page 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations...
Page 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally...
Page 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse...
Page 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse...
Page 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A...
Page 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B...
Page 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C...
Page 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC...
Page 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI...
Page 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal...
Page 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t...
Page 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t...
Page 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It...
Page 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t...
Page 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t...
Page 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT...
Page 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally...
Page 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A...