IL17569
Page 1-4
Effective June, 2001
H. Frequency
I. Power and current demand
J. Min/max values
K. Energy
• Control power
A. AC or DC control power (100–120V AC, 50/60 Hz,
or 48–125V DC)
B. Consult factory for availability of other voltage power supplies.
• Non-volatile memory for Settings, Waveforms, Sequence of Event
Logs, Trip Logs and Trending
• Determine condition of acquired data relative to settings
A. Current, voltage and frequency protection
• Monitoring and reporting of additional system information
A. Oscillography
B. Sequence of events recording
C. Trip target data
D. Real-time clock
E. Breaker wear, trip coil
F. Signal harmonic content
• Zone interlocking
• User access to processed data (through PowerNet and
PowerPort)
• Meets ANSI, IEC, UL, CUL standards
Communication Features
• Local HMI
• Addressable
• Local Communication Port (RS-232 on 9-pin DIN)
• Remote communication ports
A. Incom FSK
• Protocols
A. INCOM/IMPACC Communications Standard, IL 17384 –
Part A, version 3.0
Self-Test Features
• Hardware
A. Processor integrity
B. RAM
C. PROM checksum
D. Analog input circuitry
• Application
A. Comparison of current flow with apparent state of breaker
B. Comparison of apparent and set phase sequence
C. Determination of correct voltage or current phasor relation-
ships and/or balance
D. Setting integrity
1.8 Ordering Information
The FP-5000 and a wide variety of related and support products
may be obtained from Cutler-Hammer. Order information for
the FP-5000 is:
Style Number
Catalog Number
Option Description
66D2041G01
FP5000-00
5A Ct
48 – 125V DC,
100 – 120V AC
Power supply
standard comm.
board
66D2041G02
FP5100-00
1A Ct
48 – 125V DC,
100 – 120V AC
Power supply
standard comm.
board
Renewal Parts
66D2038G01
FP5000-00-IC
Relay Inner
Chassis 5A
66D2038G02
FP5100-00-IC
Relay Inner
Chassis 1A
66D2039G01
FP5XX0-OC
Outer Chassis for
FP5XX0-00 IC
World-wide users may determine their Cutler-Hammer sales office
by web browsing to:
http://www.ch.cutler-hammer.com/international/sales.html
In North America, web browse to:
http://www.ch.cutler-hammer.com/international/
northamerica.html
In the USA or Canada, contact your Cutler-Hammer Sales office by
calling 800-525-2000 for the location of your nearest sales office or
click your location on the web map at:
http://www.ch.cutler-hammer.com/support/index.html
Summary of Contents for Cutler-Hammer FP-5000
Page 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay...
Page 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally...
Page 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application...
Page 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application...
Page 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally...
Page 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally...
Page 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally...
Page 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations...
Page 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally...
Page 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse...
Page 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse...
Page 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A...
Page 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B...
Page 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C...
Page 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC...
Page 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI...
Page 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal...
Page 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t...
Page 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t...
Page 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It...
Page 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t...
Page 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t...
Page 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT...
Page 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally...
Page 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A...