Page 12-9
IL17569
Effective June, 2001
All contact output changes will be logged in the event log and no programming is necessary. If more than one relay changes state at exactly
the same time because of a single causal event activating more than one relay, only one log is entered into the event log. Table 12.8
summarizes all output event causes that will be logged.
Table 12.8 Event Output Cause Table
Cause
Cause Description
Value Given
Relay Changed
One of the first 6 relays – Trip 1, Trip 2,
Output Status – contains the status flag for
Rly3, Rly4, Rly5, or Alarm – has changed state
all contact outputs
Healthy State
The Relay Healthy contact output
Output Status – contains the status flag for
has changed state
all contact outputs
Breaker commands that come through the FP-5000, breaker state changes and breaker alarms are all logged automatically in the event log.
Table 12.9 shows all possible causes for breaker event logs.
Table 12.9 Event Breaker Cause Table
Cause
Cause Description
Value Given
Open Breaker
An Open Breaker command is given
Breaker Status – contains all the flags
remotely or through the front panel pushbutton
related to the breaker
Close Breaker
A Close Breaker command is given remotely
Breaker Status – contains all the flags
or through the front panel pushbutton
related to the breaker
Bkr Opened
The Breaker State is determined to be Opened
Breaker Status – contains all the flags
related to the breaker
Bkr Closed
The Breaker State is determined to be Closed
Breaker Status – contains all the flags
related to the breaker
Bkr Lockout
The Breaker has failed to break the current
Breaker Status – contains all the flags
in the programmed amount of time
related to the breaker
Bkr Time Alm
The Breaker has taken more than 40 cycles
Breaker Status – contains all the flags
to close or more than 30 cycles to open
related to the breaker
Bkr State Alm
There is a state disagreement between
Breaker Status – contains all the flags
the 52A and 52B contact inputs.
related to the breaker
Trip1 Mntr Alm
The Breaker is determined to be in the closed
Breaker Status – contains all the flags
state and no trickle open (trip) coil current
related to the breaker
is sensed around the Trip 1 contact output
Trip2 Mntr Alm
The Breaker is determined to be in the open
Breaker Status – contains all the flags
state and no trickle close coil current is
related to the breaker
sensed around the Trip 2 contact output
Whenever the communication variable input changes, if so programmed, it will be logged in the event log.
Table 12.10 shows the cause for this event log.
Table 12.10 Event Communication Cause Table
Cause
Cause Description
Value Given
CommLogic Alt
Communication Logic variable has
Communication Logic Status – contains all
changed state
4 communication logic variable states
Summary of Contents for Cutler-Hammer FP-5000
Page 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay...
Page 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally...
Page 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application...
Page 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application...
Page 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally...
Page 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally...
Page 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally...
Page 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations...
Page 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally...
Page 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse...
Page 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse...
Page 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A...
Page 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B...
Page 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C...
Page 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC...
Page 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI...
Page 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal...
Page 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t...
Page 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t...
Page 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It...
Page 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t...
Page 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t...
Page 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT...
Page 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally...
Page 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A...