Page 4-23
IL17569
Effective June, 2001
4.6.6 Test
The “Test” pushbutton can be accessed through
the security door on the front panel (see
Figure
4-1
). Once the “Test” pushbutton is activated, a
password screen will show up on the display.
The default password is “0000.” Press Enter to
enter the “Test Mode.” The “Test Mode” allows
the user to initiate current simulation tests,
operate output relays, open or close the
breaker, and test the Zone Interlocking outputs.
See Section 11 for complete details on the “Test
Mode” operation.
4.7 LEDs
The LEDs are used to indicate a number of functions, operations,
and/or warnings of the FP-5000. Please refer to
Figure 4-1
for each
LED location.
Operational LED
The Operational LED is a green flashing LED that flashes for a 1
second period, 50% duty cycle. It indicates that the FP-5000 is
operational.
Breaker Closed LED
The red Breaker Closed LED indicates that the circuit breaker is
closed based on the state of the 52a and 52b inputs.
Breaker Open LED
The green Breaker Open LED indicates that the circuit breaker is
open based on the state of the 52a and 52b inputs.
Phase Trip LED
The red Phase Trip LED indicates that a phase overcurrent trip
condition has occurred if the 50P-1, 50P-2, or 51P protective
functions operate.
Ground Trip LED
The red Ground Trip LED indicates that a ground overcurrent trip
condition has occurred if the 50X-1, 50X-2, 50R-1, 50R-2, 51X,
or 51R protective functions operate.
Other Trip LED
The red Other Trip LED indicates that a trip condition other than
phase or ground overcurrent has occurred.
Alarm LED
The red Alarm LED indicates that an alarm condition has
occurred as programmed in the alarm indicator.
Pickup LED
The yellow Pickup LED indicates the presence of a pickup
condition as programmed in the pickup indicator.
Auxiliary LED
The function of the yellow Auxiliary LED is user defined. The
logic functions may be used to control the state of this LED,
which is based on the state of the inputs programmed for the
Aux LED output.
Set LED
The red set LED located at the right upper corner of the “Set”
pushbutton indicates that the relay is in the program settings
mode.
Test LED
The red test LED at the right upper corner of the “Test”
pushbutton indicates that the relay is in the test mode. The test
LED flashes while a fault simulation is in progress.
Summary of Contents for Cutler-Hammer FP-5000
Page 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay...
Page 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally...
Page 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application...
Page 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application...
Page 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally...
Page 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally...
Page 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally...
Page 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations...
Page 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally...
Page 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse...
Page 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse...
Page 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A...
Page 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B...
Page 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C...
Page 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC...
Page 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI...
Page 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal...
Page 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t...
Page 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t...
Page 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It...
Page 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t...
Page 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t...
Page 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT...
Page 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally...
Page 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A...