IL17569
Page 5-4
Effective June, 2001
Table 5.1 System Config (continued)
Display Setting
Description
Setpoint Range/
Default
Selected
Refer to
Value Selection
Setting
Value
Sec. #
Prg w/Bkr:
Program relay with breaker
Open or Either
Either
5.5.1
open or closed (requires 52a
or 52b input)
Remote Bkr:
Enable or disable remote
Enable or disable
Disable
5.5.1
breaker open/close control
from rear comm port
# Set Grps:
Select the max. number
1, 2, 3, or 4
1
1
5.5.1
of different Protection
9.7
Setting Groups
Set Ctrl:
Select the means of control for
Local, Local+
Local
5.5.1
selecting the active setting group
Communications,
9.7
Communications, Cin
Disarm Ctrl:
Enable/disable of the
Enable or disable
2
Disable
5.5.1
Arm/Disarm control from the front
11.2.5.1
panel “Test Mode” (Output Trip1
& Trip2 ONLY)
Energy Unit:
This is the selection for “Energy
kWh or MWh
kWh
5.5.1
Units” killo- or Mega- Watt-hours
4.6.1.3
TOC Reset T:
Time Overcurrent RESET Time
1 to 20 cycles
4
5
5.5.1
Delay in cycles. Used when time
(Increments of 1)
5.5.2.1
option for reset is chosen
8.3.2
Bkr Oper PB:
Front panel Breaker Open/Close
Enable or disable
Disable
5.5.1
pushbutton function Enable
1
This setting affects other settings. The user must save settings after changing this setting, which will take the user
out of program mode. The user must then re-enter program mode to continue programming the remaining settings.
2
If enabled, the user must go to the “Test Mode” by pressing the “test button”, select Arm/Disarm Trip, then select
Arm Trip or Disarm Trip setting.
3
Ct secondary rating is automatically detected: I
nom
= 1A or 5A.
4
This setting is the programmed time delay for the T Delay setting of the time overcurrent Reset setting. See TOC
Curve settings for 51P, 51R, and 51X elements.
Summary of Contents for Cutler-Hammer FP-5000
Page 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay...
Page 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally...
Page 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application...
Page 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application...
Page 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally...
Page 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally...
Page 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally...
Page 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations...
Page 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally...
Page 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse...
Page 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse...
Page 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A...
Page 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B...
Page 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C...
Page 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC...
Page 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI...
Page 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal...
Page 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t...
Page 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t...
Page 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It...
Page 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t...
Page 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t...
Page 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT...
Page 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally...
Page 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A...