Instructions for the FP-6000 Protective Relay
Table 25. LED Config: Select LED Configuration Settings (LED1 to LED8) (continued).
See tables 53 through 56 for the definitions of the options.
DISPLAY SETTING
DESCRIPTION
SETTING RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
Pickup Indicator
Output Pickup Indicator Settings
9.2
9.6
Dropout:
Select pickup indictor dropout
Latched, unlatched
Unlatched
IOC:
Enable or disable IOC pickup indicator
Disable, enable
Enable
TOC:
Enable or disable TOC pickup indicator
Disable, enable
Enable
Volt:
Enable or disable voltage pickup indicator
Disable, enable
Enable
OverFreq:
Enable or disable overfrequency pickup
indicator
Disable, enable
Enable
UnderFreq:
Enable or disable underfrequency pickup
indicator
Disable, enable
Enable
Unbalance:
Enable or disable voltage/current unbalance
pickup indicator
Disable, enable
Enable
Power:
Enable or disable power pickup indicator
Disable, enable
Enable
Prot Alarm:
Enable or disable protection pickup indica-
tor
Disable, enable
Disable
RTD
Enable or disable RTD pickup indicator
Disable, enable
Disable
Table 26. LED Logic Input (IN1, IN2, IN3 & IN4) Programming Option Settings: Logic Input Settings for the 9
Logic Categories.
INPUT CATEGORY
"AVAILABLE SETTING OPTIONS"
SETPOINT RANGE/
VALUE SELECTION
Unused
Unused
Direct or Negated
Pickup
PH OC, G OC, IOC, TOC, OC, All Alm, Volt, Freq, AllProt, 50X-1, 50X-2, 50X-3,
50R-1, 50R-2, 50R-3, 50P-2, 50P-3, 51P-1, 51P-2, 51P, 51X, 51R, 59A-1, 59A-2,
27A-1, 27A-2, 59M-1, 59M-2, 27M-1, 27M-2, 46-1, 46-2, 47-1, 47-2, 81U-1, 31U-
2, 81O-1, 81O-2, BF, 55A, 55D, 55N-1, 59N-2, 32-1, 32-2, 32-3, LOP, LOPB
49DTG1, 49DTG2, 49DT1, 49DT2, 48DT3, 49DT4, 49DT5, 49DT6, 49DT7, 49DT8,
49DT9, 49DT10, 49DT11, 49MT, 49DA11, 49DA21, 49DA31, 49DA41, 49DA51,
49DA61, 49DA71, 49DA81, 49DA91, 49DAA1, 49DAB1, 49MA1, 49DA12,
49DA22, 49DA32, 49DA42, 49DA52, 49DA62, 49DA72, 49DA82, 49DA92,
49DAA2, 49DAB2, 49MA2, 32V-1, 32V-2, 32V-3
Direct or Negated
Trip
PH OC, G OC, IOC, TOC, OC, All Alm, Volt, Freq, AllProt, 50X-1, 50X-2, 50X-3,
50R-1, 50R-2, 50R-3, 50P-2, 50P-3, 51P-1, 51P-2, 51P, 51X, 51R, 59A-1, 59A-2,
27A-1, 27A-2, 59M-1, 59M-2, 27M-1, 27M-2, 46-1, 46-2, 47-1, 47-2, 81U-1,
31U-2, 81O-1, 81O-2, BF, 55A, 55D, PhZone, GndZone, 59N-1, 59N-2, 32-1, 32-2,
32-3, LOPA, 49DTG1, 49DTG2, 49DT1, 49DT2, 48DT3, 49DT4, 49DT5, 49DT6,
49DT7, 49DT8, 49DT9, 49DT10, 49DT11, 49MT,49DA11, 49DA21, 49DA31,
49DA41, 49DA51, 49DA61,9DA71, 49DA81, 49DA91, 49DAA1, 49DAB1,
49MA1,49DA12, 49DA22, 49DA32, 49DA42, 49DA52, 49DA62,49DA72, 49DA82,
49DA92, 49DAA2, 49DAB2, 49MA2,32V-1, 32V-2, 32V-3
Direct or Negated
Logic
LG1, LG2, LG3, L54, LG5, LG6, TG1, TG2, TG3, TG4, TG5, TG6, OG1, OG2, OG3,
OG4, OG5, OG6, OG7
Direct or Negated
Inputs
Cin1, Cin2, Cin3, Cin4, Cin5, Cin6, Cin7, Cin8 or ZI In
Direct or Negated
SysAlm
Power, Power Demand, Current Demand, % THD, Bkr Ops,
Σ
I, All Alm,
BkrOPH, BkrAlm, BkrLoc
Direct or Negated
Breaker Control
OpenBkr, CloseBkr, Open, Closed, BkrFail Alm, StateAlm, Mntr1Alm,
Mntr2Alm, All Alm, 67G-F, 67G-R, 67V_F, 67V_R, 67Q_F, 67Q_R, 67I_F, 67I_R,
67X-F, 67X-R, 67VIXF, 67VIXR, 67A-F, 67B-F, 67C-F, InSync, SyncFail, SlipAlm,
25BL, 25LL, Coldload, 79RUN, 79BLCK, 79Lock, 79Fail, 79SH1, 79SH2, 79SH3,
79SH4, 79AntiP
Direct or Negated
Comm
Comm1, Comm2, Comm3 or Comm4
Direct or Negated
Display
Monitor, View, Log, Status, Set, Test
Direct or Negated