Instructional Literature
Page
68
Effective: May 2008
Instructions for the FP-6000 Protective Relay
For more information visit: www.eaton.com
IB02602004E
Table 12. Protection (continued).
Power Factor:
Selects Apparent PF (55A) and Displacement PF (55D) device settings.
DISPLAY SETTING
DESCRIPTION
SETPOINT RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
55A Apparent PF
Apparent Power Factor Settings
5.4.2.9
Trigger PF:
Select power factor to trigger on
0.50 to 1.00 (lag), -0.50 to -.99 (lead), disable
(0.01pu increments)
Disable
Resent PF:
Select power factor to reset on
0.50 to 1.00 (lag), -0.50 to -.99 (lead), disable
(0.01pu increments)
Disable
Delay (s):
Select delay time in seconds
0 to 1000 seconds
(1 second increments)
0
55D Displacement PF
Displacement Power Factor Settings
5.4.2.9
Trigger PF:
Select power factor to trigger on
0.50 to 1.00 (lag), -0.50 to -.99 (lead), disable
(0.01pu increments)
Disable
Reset PF:
Select power factor to reset on
0.50 to 1.00 (lag), -0.50 to -.99 (lead), disable
(0.01pu increments)
Disable
Delay (s):
Select delay time in seconds
0 to 1000 seconds
(1 second increments)
0
Zone Interlocking:
Selects Zone In and Zone Out settings.
DISPLAY SETTING
DESCRIPTION
SETPOINT RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
Zone Interlock Trip
Zone Interlock Trip Settings
5.4.2.10
8.5
Phase or Ground:
Select zone interlock trip function
Disable, Phase, Ground, Both
Disable
Direction:
Select zone interlock trip direction
Fwd, Rev or Both
Both
Zone Interlock Out
Zone Interlock Out Settings
5.4.2.10
8.5
Phase or Ground:
Select zone interlock out function
Disable, Phase, Ground, Both
Disable
Direction:
Select zone interlock out direction
Fwd, Rev or Both
Both