Instructional Literature
Page
76
Effective: May 2008
Instructions for the FP-6000 Protective Relay
For more information visit: www.eaton.com
IB02602004E
Table 13. System Alarms.
DISPLAY SETTING
DESCRIPTION
SETTING RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED VALUE REFER TO SEC. #
Watt Power Alarm
System Watt Power Alarm Setting
5.4.3
Units:
Select units for watt power
kW or MW
kW
Threshold:
Select magnitude threshold in primary units
1 to 40,000, Disable (incre-
ments of 1)
Disable
Delay (m):
Select delay time in minutes
0 to 60 minutes (increments of
1)
0
VAR Power Alarm
System VAR Power Alarm Setting
5.4.3
Units:
Select units for VAR power
kVAR or MVAR
kVAR
Threshold:
Select magnitude threshold in primary units
1 to 40,000, Disable (incre-
ments of 1)
Disable
Delay (m):
Select delay time in minutes
0 to 60 minutes (increments of
1)
0
VA Power Alarm
System VA Power Alarm Setting
5.4.3
Units:
Select units for VA power
kVA or MVA
kVA
Threshold:
Select magnitude threshold in primary units
1 to 40,000, Disable (incre-
ments of 1)
Disable
Delay (m):
Select delay time in minutes
0 to 60 minutes (increments of
1)
0
Watt Demand Alarm
System Watt Demand Alarm Setting
5.4.3
Units:
Select units for watt demand
kW or MW
kW
Threshold:
Select magnitude threshold in primary units
1 to 40,000, Disable (incre-
ments of 1)
Disable
Delay (m):
Select delay time in minutes
0 to 60 minutes (increments of
1)
0
VAR Demand Alarm
System VAR Demand Alarm Setting
5.4.3
Units:
Select units for VAR demand
kVAR or MVAR
kVAR
Threshold:
Select magnitude threshold in primary units
1 to 40,000, Disable (incre-
ments of 1)
Disable
Delay (m):
Select delay time in minutes
0 to 60 minutes (increments of
1)
0
VA Demand Alarm
System VA Demand Alarm Setting
5.4.3
Units:
Select units for VA demand
kVA or MVA
kVA
Threshold:
Select magnitude threshold in primary units
1 to 40,000, Disable (incre-
ments of 1)
Disable
Delay (m):
Select delay time in minutes
0 to 60 minutes (increments of
1)
0
Current Demand Alarm
System Current Demand Alarm Setting
5.4.3
Pickup:
Select pickup in primary units
10 to 10,000 amps, Disable
(increments of 10)
Disable
Delay (m):
Select delay time in minutes
0 to 60 minutes (increments of
1)
0
I THD Alarm
System Current Total Harmonic Distortion Alarm
Setting
5.4.3
Threshold:
Select magnitude of I THD in primary units
(Phase CT Primary/100) to
(Phase CT Primary *10)
[increments of Phase CT
Primary/100]
Disable
Delay (m):
Select delay time in minutes
0 to 3600 second (increments
of 1s)s
0
V THD Alarm
System Voltage Total Harmonic
Distortion Alarm Setting
5.4.3
Threshold:
Select magnitude of V THD in primary units
Main VTR/10 to
Main VTR *10
(increments of
Main VTR/100)
Disable
Delay (m):
Select delay time in minutes
0 to 3600 seconds (increments
of 1s)
0