I.L. 17567
Effective January, 2000
THE MODULE
The Separate Source Power Supply Module
(IQMSSPM) is designed for use with the
IQA6400/IQA6600 (66d2045) and DP4000 (66d2040)
meters in three-phase applications to 600Vac. The
IQMSSPM will power either of these devices from 100-
240 Vac or 100-250 Vdc.
In applications using either the IQA6400/IQA6600 or the
DP4000/DP4100, supply power can be converted from
three-phase power to a separate single-phase supply,
station battery, or UPS.
The IQMSSPM may also be used in certain applications
of the IQA6000/6200 (2d82302) or DP4000/DP4100
(4d13110) where the NEU terminal is grounded. These
applications include three-wire applications and
applications with potential transformers (PT’s). In either
of these acceptable retrofit applications, the NEU to
GND potential at the meter terminals is zero.
INSTALLATION
This device is designed to be installed, operated, and
maintained by adequately trained personnel. These
instructions do not cover all details, variations, or
combinations of the equipment, its storage, delivery,
installation, checkout, safe operation, or maintenance.
Care must be exercised to comply with local, state, and
national regulations, as well as safety practices, for this
class of equipment.
REMOVE ALL POWER FROM (DE-ENERGIZE) THE
DEVICE TO WHICH THE POWER MODULE IS BEING
ATTACHED OR WIRED; OTHERWISE, SERIOUS OR
FATAL PERSONAL INJURY AND EQUIPMENT
DAMAGE MAY RESULT.
REMOVING EXISTING POWER MODULE
Disconnect all power to the existing meter, including
power to any relay contacts of the device. Clearly mark
wire connections to the voltage terminal block. Refer to
Fig. 2 and your meter’s technical manual. If replacing
an existing Separate Source Power Module, clearly
mark the wire connections to the power connection
terminal block. Disconnect all wires from the existing
power module.
Unscrew the plug lock assembly on the ribbon cable
from the meter chassis and remove the cable from the
power module connector. Carefully remove the two
shoulder screws that secure the power module to the
chassis.
BE PREPARED TO SUPPORT THE POWER MODULE
ONCE THE SCREWS HAVE BEEN REMOVED.
MOUNTING TO IQ ANALYZER OR DP4000
Place the Separate Source Power Module in its
mounting position on the rear of the meter chassis, in
the same position as the one removed. Replace the two
shoulder screws to secure the IQMSSPM. Reconnect all
wires to the IQMSSPM and meter - tighten all screws.
Fig. 1 Separate Source Power Module
Instructions for Separate Source Power Module:
Style IQMSSPM (66C2105)
CAUTION
CAUTION