LCX9000 Liquid-Cooled Drives User Manual
3-6
For more information visit:
www.EatonElectrical.com
MN04005001E
January 2007
Table 3-6: Fuse Sizes for LCX9000 Liquid-Cooled (690V) Drives
Tj = 77°F (25°C).
SHT fuses can be assembled into DIN fuse base of the corresponding size.
Note:
Data in italic refer to drives with 12-pulse supply.
Fuse information
Max fuse ambient tempe122°F (+50ºC).
Fuse sizes can differ in the same chassis. Fuses can be chosen according to the highest
current rating of the chassis to minimize fuse variants.
Check the current rating of the fuse bases according to the input current of the drive.
The physical size of the fuse is chosen on the basis of the fuse current: Current <400 amps
(size 2 fuse or smaller), current <400 amps (size 3 fuse).
Chassis
Catalog
Number
I
th
(A)
DIN43620
DIN43653 (80 mm)
DIN43653 (110 mm)
Fuse
U
n
(V)
Fuse
I
n
(A)
Qty. of
Fuses per
Phase
3~
aR Fuse
Part No.
Fuse
Size
aR Fuse
Part No.
Fuse
Size
aR Fuse
Part No.
Fuse
Size
CH61
LCX170A0-5
170 170M3819 DIN1
170M3069 1xTN/80 170M3219 1xTN/110 690
400 1
LCX208A0-5
208 170M3819 DIN1
170M3069 1xTN/80 170M3219 1xTN/110 690
400 1
LCX261A0-5
261 170M3819 DIN1
170M3069 1xTN/80 170M3219 1xTN/110 690
400 1
CH72
LCX325A0-5
325 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 1
LCX325A0-5
325 170M3819 DIN1
170M3069 1xTN/80 170M3219 1xTN/110 690
400 2
LCX385A0-5
385 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 1
LCX385A0-5
385 170M3819 DIN1
170M3069 1xTN/80 170M3219 1xTN/110 690
400 2
LCX416A0-5
416 170M6812 DIN3
170M6062 3TN/80
170M6212 3TN/110
690
800 1
LCX416A0-5
416 170M3819 DIN1
170M3069 1xTN/80 170M3219 1xTN/110 690
400 2
LCX460A0-5
460 170M6812 DIN3
170M6062 3TN/80
170M6212 3TN/110
690
800 1
LCX460A0-5
460 170M3819 DIN1
170M3069 1xTN/80 170M3219 1xTN/110 690
400 2
LCX502A0-5
502 170M6812 DIN3
170M6062 3TN/80
170M6212 3TN/110
690
800 1
LCX502A0-5
502 170M3819 DIN1
170M3069 1xTN/80 170M3219 1xTN/110 690
400 2
CH63
LCX590A0-5
590 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1100 1
LCX650A0-5
650 170M8547 3SHT
170M6066 3TN/80
170M6216 3TN/110
690
1250 1
LCX750A0-5
750 170M8547 3SHT
170M6066 3TN/80
170M6216 3TN/110
690
1250 1
CH74
LCX820A0-5
820 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 3
LCX820A0-5
820 170M6812 DIN3
170M6062 3TN/80
170M6212 3TN/110
690
800 2
LCX920A0-5
920 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 3
LCX920A0-5
920 170M6812 DIN3
170M6062 3TN/80
170M6212 3TN/110
690
800 2
LCXH10A0-5
1030 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 3
LCXH10A0-5
1030 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 2
LCXH11A0-5
1180 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 3
LCXH11A0-5
1180 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 2
LCXH13A0-5
1300 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 3
LCXH13A0-5
1300 170M8547 3SHT
170M6066 3TN/80
170M6216 3TN/110
690
1250 2
LCXH15A0-5
1500 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 3
LCXH15A0-5
1500 170M8547 3SHT
170M6066 3TN/80
170M6216 3TN/110
690
1250 2