LCX9000 Liquid-Cooled Drives User Manual
MN04005001E
For more information visit:
www.EatonElectrical.com
4-13
January 2007
Table 4-2: Installing the Control Unit Mounting Box (Continued)
Internal Connections
As a general rule, all internal electrical and communications connections are made at the
factory. However, if modules have to be moved, for example, and the connections therefore
removed, you will have to re-establish the connections between 1) the Power Unit ASIC and
the Driver Board(s) on the one hand and 2) the Power Unit ASIC and the Optical Cable
Adapter Board on the other.
Connections between Power Unit ASIC and Driver Boards
See the figures and tables on the following pages for the correct connection of internal
electrical and communications connections.
Note:
The minimum optical cable bending radius is 1.97 inches (50 mm).
7. Connect the female end of the keypad
cable to keypad on the enclosure door.
8. Use a cable channel for the cable run.