background image

For more information visit: www.cutler-hammer.eaton.com

IB01602007E

Instruction Bulletin

Page

 14

Effective:  June 2003

O&M Manual for 
Non-Automatic Transfer 
Switches (30 – 1200 Amperes)

Section 4:  Installation and Wiring

4.1  General

Transfer switches are factory wired and tested. Installation 
requires solidly mounting the enclosed unit and connecting 
power cables and auxiliary pilot circuits. Physical mounting 
procedures and power cable connections are covered in 
this section. All other required wiring or electrical connec-
tion references are covered in a separate 

Quick Start Guide

 

packed with the transfer switch. Locate the wiring booklet, 
review it, and keep it readily available for reference purposes 
during installation and testing. Once a transfer switch is 
properly installed and wired, it should be mechanically and 
electrically checked for proper installation and operation. 
The procedures for these initial mechanical and electrical 
checks are outlined in Section 6 of this instruction bulletin.

To facilitate the procedures described in this section for the 
vertical design, remove the solid steel shield over the power 
panel. The shield is attached to the ratchet assembly with 
four screws. Remove the four screws and shield until the 
procedures are completed.

4.2  Mounting Location

Choose a location that offers a flat, rigid mounting surface 
capable of supporting the weight of the enclosed transfer 
switch equipment. Avoid locations that are moist, hot and/or 
dusty. Enclosure designs are, however, available for special 
environments. If there are any doubts as to location suitabil-
ity, discuss it with your Cutler-Hammer representative.

Check to make certain that there are no pipes, wires or other 
mounting hazards in the immediate mounting area that 
could create a present or future problem.

Carefully remove all packing material from the transfer 
switch at the mounting location. Even though an equipment 
inspection was made when the equipment was received, 
make another careful inspection of the enclosure and the 
enclosed transfer switch as packing material is removed 
and the enclosure readied for mounting. Be especially alert 
for distorted metal, loose wires or damaged components.

4.3  Mounting Procedure

All transfer switch equipment enclosures are of the same 
design. Only the overall physical dimensions change. The 
enclosure is provided with four elongated mounting holes, 
two in the top mounting flange and two in the bottom. 

If the transfer switch equipment is of the vertical design, the 
power panel is provided with two sets of mounting holes. 
One set positions the panel for top entry of cables and one 
set for bottom entry (Figure 13). This will be covered in more 
detail later in Section 4.4 Vertical Design Load Lug Location.

Transfer switch equipment is assembled and supplied as 
standard for top entry, although equally adaptable to bottom 
entry. Cable entry holes are not part of the enclosure when 
shipped from the factory and must be provided in the field, 
either before or after mounting the enclosure.

NOTICE

WARNING

BE CERTAIN THAT THE SOLID STEEL POWER PANEL 
SHIELD USED WITH THE VERTICAL DESIGN IS PROPERLY 
INSTALLED BEFORE TRANSFER SWITCH EQUIPMENT IS 
PUT INTO SERVICE. THE SHIELD PROVIDES PROTECTION 
FROM DANGEROUS VOLTAGES AT THE LINE AND LOAD 
TERMINALS WHEN THE EQUIPMENT IS IN OPERATION. 
FAILURE TO DO SO COULD RESULT IN PERSONAL 
INJURY OR DEATH.

CAUTION

SINCE THE ENCLOSED TRANSFER SWITCH MUST BE 
LIFTED INTO PLACE FOR MOUNTING, BE CERTAIN THAT 
ADEQUATE RESOURCES ARE AVAILABLE FOR LIFTING TO 
AVOID PERSONNEL INJURIES OR EQUIPMENT DAMAGE.

CAUTION

EXTREME CARE SHOULD BE TAKEN TO PROTECT THE 
TRANSFER SWITCH FROM DRILL CHIPS, FILINGS AND 
OTHER CONTAMINANTS WHEN MAKING THE CABLE 
ENTRY HOLES AND MOUNTING THE ENCLOSURE 
TO PREVENT COMPONENT DAMAGE OR A FUTURE 
MALFUNCTION.

Summary of Contents for Cutler-Hammer NTV Series

Page 1: ...IB01602007E For more information visit www cutler hammer eaton com O M Manual for Non Automatic Transfer Switches 30 1200 Amperes Instruction Bulletin New Information...

Page 2: ...PROVIDED ON THE NAMEPLATE A TYPICAL EQUIPMENT NAMEPLATE IS SHOWN IN FIGURE 1 Automatic Transfer Switch Cat No NTVEKDB0300X54 06 03 GO No Item 1 1 of 1 E Poles 3 Amps 300 Volt 480 Phase 3 Hertz 60 Wir...

Page 3: ...ic Panel Door Mounted 11 11 Charger Mounting Dimensions in Inches mm 12 12 Typical NEMA Type 1 Enclosure Door Closed 13 13 Vertical Design Power Panel Mounting Reference in Inches mm 15 14 Vertical De...

Page 4: ...power from one of these two sources In the event that power is lost from the normal power source the transfer switch transfers the load to the secondary emergency power source Trans fer can be automat...

Page 5: ...r Switch was designed with installation ease and simplified maintenance in mind Three main panels comprise the automatic transfer switch design Power Panel Voltage Selection Panel Logic Panel Each pan...

Page 6: ...tch Electrically Operated Switching Device Orientation V Vertical 1 H Horizontal 2 Control Panel E Electromechanical Number of Poles 2 Two 3 Three 4 Four Ampere Rating 30A 0030 70A 0070 100A 0100 150A...

Page 7: ...option which includes specially designed cleats transfer switches have a seismic capability which exceeds the worst case Zone 4 required levels per both the Uniform Building CodeT and the California B...

Page 8: ...otectors over the indicating light panel and operating handle A heavy duty cardboard lid covers the entire opening The shipment is secured and further protected with shrink wrap Do not discard the pac...

Page 9: ...d automatic transfer switch encompasses all transfer switch equipment possibilities it is the only specific type that will be discussed in this section Figure 6 Typical Vertical Design Power Panel Unm...

Page 10: ...s from being closed simultaneously The load side contacts of each switching device are joined with a bus bar assembly to form a common load terminal location either top or bottom Figure 14 Horizontall...

Page 11: ...ges taps from 208 600 Vac satisfy any required application voltage A quick change capability from one voltage to another is provided by a small disconnect plug 3 4 Logic Panel The logic panel provides...

Page 12: ...12 volts D 24 volts When supplied the battery charger is provided in a separate wall mounted enclosure Figure 11 Separate instructions and wiring information are provided with the charger for installa...

Page 13: ...switch equipment enclosed in a NEMA 1 enclosure is UL listed for application In addition Cutler Hammer Transfer Switches are listed in File E38116 by Underwriters Laboratories Inc under Standard UL 10...

Page 14: ...Carefully remove all packing material from the transfer switch at the mounting location Even though an equipment inspection was made when the equipment was received make another careful inspection of...

Page 15: ...the two upper mounting bolts in the mounting surface Step 3 Gently lift the enclosure and guide the elongated holes in the upper mounting flange over the upper mounting bolts but do not completely tig...

Page 16: ...ill facilitate re installation of the power panel Step 4 Remove the operating mechanism from the front of the power panel by removing the six bolts holding the mechanism in position The molded case sw...

Page 17: ...glass poly ester phase barriers are in place and positioned properly in the grooves provided When making any bolted connection to the bus comply with the torque requirements as outlined in Table 3 Ta...

Page 18: ...nting holes in the power panel with the pre tapped inserts in the rear of the enclosure Step 10 With the power panel held securely against the back of the enclosure replace and tighten the four mounti...

Page 19: ...identified on the label affixed to the unit immediately adjacent to the lugs Step 7 Make necessary connections of options using wiring diagrams and Quick Start Guide supplied with the unit Table 4 Tr...

Page 20: ...vertical design transfer switch is furnished with a multi tap Voltage Selection Panel to the right of the power panel Seven front accessible taps from 208 to 600 Vac are provided Figure 9 A small disc...

Page 21: ...zes a mechanical mechanism with a manual operating handle Figure 15 The manual operating handle can be used to create the rota tional motion required to open and close the main contacts through a rigi...

Page 22: ...d to a transfer motor Figure 16 A slide pin engaging a pivot in the rotating lever converts rotary motion to linear motion To operate breaker manually or if the breaker trips unplug P3 from S3 to disc...

Page 23: ...pened or closed electrically There is however no intelligence circuit associated with this design Electrical operation is accomplished by adding a motor and required circuitry to the manual mechanism...

Page 24: ...mpany 6 Basic description of situation as it exists 7 Any results of problem solving steps taken and or readings taken 6 2 1 Transfer Switch Appears Inoperative Step 1 Verify that all plugs and socket...

Page 25: ...ake certain that any accessory control power is switched off by disconnecting all logic plugs B Inspect structure area for safety hazards or potential maintenance problems Inspect area especially wher...

Page 26: ...OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will the Cutler Hammer business be responsible to the purchaser or user in...

Page 27: ...2007E For more information visit www cutler hammer eaton com Instruction Bulletin Effective June 2003 Page 27 O M Manual for Non Automatic Transfer Switches 30 1200Amperes This page intentionally left...

Page 28: ...Transfer Switches 30 1200Amperes 2003 Eaton Corporation All Rights Reserved Printed in USA Publication No IB01602007E June 2003 Eaton Corporation Cutler Hammer business unit 1000 Cherrington Parkway M...

Reviews: