SLX9000 Adjustable Frequency Drives User Manual
MN04003020E
For more information visit:
www.eaton.com
9-3
January 2009
2.1.14 I/O Reference selection
ID117
Defines the selected frequency reference source when the drive is controlled from
the I/O terminal.
0
AI1 reference (terminals 2 and 3, e.g. potentiometer)
1
AI2 reference (terminals 5 and 6, e.g. transducer)
2
Keypad reference (parameter R3.2)
3
Reference from Fieldbus (FBSpeedReference)
4
Motor potentiometer reference
5
AI1/AI2 selection. Selection of AI2 is made programmable by DIN3
Function (P2.1.18)
2.1.15 AI2 (I
in
) signal range
ID390
1
Signal range 0 – 20 mA
2
Signal range 4 – 20 mA
3
Signal range 0 – 10V
4
Signal range 2 – 10V
Note:
The selections have no effect if par. 2.2.12 > 0%, or par. 2.2.13 < 100%.
2.1.16 Analog output function
ID307
This parameter selects the desired function for the analog output signal.
See
Table 8-5
for the parameter values.