COMMUNICATIONS
Two accessory communication modules, called WPONI
and WPONIDNA, are available. The WPONI provides remote
control and permits the microprocessor in the solid state
current-sensing unit of a motor starter to transmit data at
9600 baud regarding the starter via an INCOM network
that is part of an Integrated Monitoring, Protection, and
Control Communications (IMPACC) system. A typical net-
work consists of shielded wires daisy-chained to a remote
personal-size computer as shown in Figure 4. See I.L.
17408 for more information concerning the WPONI. The
WPONIDNA provides DeviceNet users with the ability to
control and monitor the functions of the Advantage system
at 125,000 baud. See I.L. 24659 for more information con-
cerning the WPONIDNA. The control functions and data
are identified at the computer by the address assigned (sel-
ected) for the motor starter and consist of the following:
FOR THE WPONI
1. Control voltage
2. ON, OFF, TRIP, and RESET functions
3. Motor current in each phase
4. Overload trip current selected
5. Manual / Automatic reset selection
6. Starter status, i.e., ON, OFF, or TRIPPED
7. Cause of trip, i.e. overcurrent, phase loss, phase
imbalance, ground current.
FOR WPONIDNA
1. Contactor position - open / closed
2. Three phase motor currents
3. Thermal capacity - percent
4. Network readable Advantage configuration
a. Trip current
b. Overload class
c. Phase loss enable / disable
d. Ground fault enable / disable
5. Percent current imbalance
6. Fault diagnostics
7. Start / Stop control
8. Remote reset
Consult the factory for information regarding other networks
that may be used with WPONI and WPONIDNA modules.
CONTROL OPTIONS
An Advantage non-reversing motor controller may be used
with two-wire control or any one of three three-wire control
schemes. The four point (3-P-E-C) terminal block shown in
Figure 3 is attached to the shock-mounted circuit board
and will give approximately 1/16 inch under screwdriver
pressure.
TABLE V - SIZE 4 CURRENT RANGE
*ALL SETTINGS NOT SHOWN ARE EQUIVALENT TO 00000
Replace the arc box cover securely after making selections.
Fig. 4 Typical Network Interwiring
Column A
Column B
Service Factor
Service Factor
DIP Switch
Trip
Setting*
Rating
(Positions
1.15 to 1.25
1.0
(Amps)
54321)
Min.
Max.
Min.
Max.
9.9
-
10.8
10.8
-
11.7
12.4
00000
10.9
-
11.9
11.8
-
12.9
13.6
00001
12.0
-
13.1
13.0
-
14.2
15.0
00010
13.2
-
14.4
14.3
-
15.6
16.5
00011
14.5
-
15.8
15.7
-
17.2
18.1
00100
15.9
-
17.4
17.3
-
18.9
19.9
00101
17.5
-
19.2
19.0
-
20.9
21.9
00110
19.3
-
21.1
21.0
-
22.9
24.1
00111
21.2
-
23.2
23.0
-
25.2
26.5
01000
23.3
-
25.6
25.3
-
27.8
29.1
01001
25.7
-
28.1
27.9
-
30.6
32.1
01010
28.2
-
30.9
30.7
-
33.6
35.3
01011
31.0
-
34.1
33.7
-
37.0
38.8
01100
34.2
-
37.5
37.1
-
40.8
42.7
01101
37.6
-
41.3
40.9
-
44.9
47.0
01110
41.4
-
45.4
45.0
-
49.4
51.7
01111
45.5
-
50.0
49.5
-
54.3
56.9
10000
50.1
-
54.9
54.4
-
59.7
62.6
10001
55.0
-
60.5
59.8
-
65.7
68.8
10010
60.6
-
66.5
65.8
-
72.3
75.7
10011
66.6
-
73.2
72.4
-
79.6
83.3
10100
73.3
-
80.7
79.7
-
87.7
91.6
10101
80.8
-
88.7
87.8
-
96.4
101
10110
88.8
-
97.5
96.5
-
105
111
10111
97.6
-
106
106
-
116
122
11000
107
-
117
117
-
127
134
11001
118
-
129
128
-
135
147
11010
130
-
135
-
162
11011
PONI MODULE
AND/OR
IMPACC DEVICES
P
N - 1
P
N
COMPUTER
WITH
CONI CARD
P
1
TELEPHONE JACK ASSEMBLY
BELDEN 9463
OR EQUIVALENT
P
2
TELEPHONE CABLE