41
Configuration Tag 19:
DigiTrip 520MC
Command
Number
INCOM
Command
Command
Description
Scan
Level
0
300
Fast Status
Poll
1
301
Primary / Secondary / Cause
Interleaved
2
30F N=3
Current Buffer
Interleaved
3
3C9
Setpoints Buffer
Timed3
Binary
Input
Type
Description
Scan
Level
0
Status
Device On-Line
Virtual
1
Status
Open (S7-S6 state = 00)
Poll
2
Status
Closed (S7-S6 state = 01)
Poll
3
Status
Tripped (S7-S6 state = 10)
Poll
4
Status
LDPU Alarm (S7-S6 state = 11)
Poll
5
Status
Breaker Closed (S6 state)
Poll
6
Status
Remote Trip (S5 state)
Poll
7
Status
Alarms Active (S0 state)
Poll
Analog
Input
Type
Description
Scan
Level
0
Data
I
A
Interleaved
1
Data
I
B
Interleaved
2
Data
I
C
Interleaved
3
Data
I
G
Interleaved
Counter
Input
Type
Description
Scan
Level
0
Data
Primary / Secondary / Cause
Interleaved
1
Data
INCOM Product ID
Poll
2
Data
Firmware Version / Revision
Timed3
Control
Output
Latch ON
Latch OFF
0
-----
-----
1
-----
-----
2
Reset Trip
-----
3
Reset Product Statistics
-----
4
Reset Power-Up Indicator
-----