Appendix C
C.1
Primary / Secondary / Cause
Binary Counter
The Primary / Secondary / Cause binary counter
object is a 32-bit encoded value. The high byte
of the high word (bits 31-24) is the primary
status as listed in
Table 11
. The low byte of the
high word (bits 23-16) is the secondary status as
listed in
Table 12
. The low word (bits 15-0) is
the cause–of–status (pertaining to the primary
status) as listed in
Table 13
.
Code
Definition
Code
Definition
0
Unknown
19
Phase A Alarm
1
Open
20
Phase B Alarm
2
Closed
21
Phase C Alarm
3
Tripped
22
Neutral Alarm
4
Alarmed
23
Ground / Earth Alarm
5
On
24
Phase AB Alarm
6
Off
25
Phase BC Alarm
7
Ready
26
Phase CA Alarm
8
Starting
27
On Good Source
9
Operational
28
Running
10
Stopped
Reserved 29 … 251
11
Locked-out
12
Transferred
13
Picked-up
14
Phase A Trip
15
Phase B Trip
252
Product Specific Code 252
16
Phase C Trip
253
Product Specific Code 253
17
Neutral Trip
254
Product Specific Code 254
18
Ground / Earth Trip
255
Product Specific Code 255
Table 11: Primary Status Code Definitions
Code
Definition
Code
Definition
0
Unknown
9
Reserved 9 … 27
1
Not applicable
2
Program mode
3
Test mode
4
Disabled
5
Disarmed
28
Product Specific Code 28
6
Controlled device failed to operate
27
Product Specific Code 29
7
Powered up
30
Product Specific Code 30
8
Alarm
31
Product Specific Code 31
Table 12: Secondary Status Code Definitions