04
/1
8
IL
04
004
9Z
U
Emergency On Call Service: Local representative
Eaton.eu/aftersales
or +49 (0) 180 5 223822 (de, en)
11/14
USA: EatonCare at
Eaton.com/eatoncare
or 877-386-2273
→
P1-13 = 11
P1-12 = 0
Input
L: 0 - 4 V DC
H: 8 - 30 V DC
Output
External 24 V DC (100 mA)
1
+24 V DC, < 100 mA
Digital Input 1 (DI1)
Stop
Enable,
Run Forward Rotation
2
Digital Input 2 (DI2)
Stop
Enable,
Run Reverse Rotation
3
Digital Input 3 (DI3)
AI1
FF1/FF2
4
5
+10 V DC, < 10 mA
Analog Input 1 (AI1): 0 - 10 V DC, < 20 mA, Frequency Setpoint value
[Digital Input 4 (DI4)] → P1-13
6
0 V
7
0 V
8
Analog Output 1 (AO1): 0 - 10 V DC, < 20 mA, Output Frequency
[Digital Output 1 (DO1)] → P2-11, P2-12
0 V
9
0 V
Digital Input 5 (DI5)
[Analog Input 2 (AI2)]
→ P1-13
FF1, Fixed Frequency
(P2-01 = 5 Hz)
FF2, Fixed Frequency
(P2-02 = 10 Hz)
10
11
Analog Output 2 (AO2): 0 - 10 V DC, < 20 mA, Output Current
[Digital Output 2 (DO2)] → P2-13, P2-14
Safe Tourqe Off
Stop
STO+ (18 - 30 V DC)
12
Safe Tourqe Off
Stop
STO- (0 V)
13
14
Relay (K11 = COM)
15
Relay (K14 = NO), Healthy
16
Relay (K12 = NC), Error
17
Relay (K23 = COM)
18
Relay (K24 = NO), RUN
→
K1
K2
EMC L1 L2 L3
EMC
DC+ BR DC-
U V W
PIN 8
(PIN 2)
PIN 7
(PIN 1)
RS485
RJ45
X1
PIN 1
CANopen -
PIN 2
C
PIN 3
OV
PIN 4
OP-Bus -
PIN 5
OP-Bus +
PIN 6
+ 24 V
PIN 7
Modbus RTU -
PIN 8
Modbus RTU +
EMC L1 L2 L3
EMC
DC+ BR DC-
U V W
1 2 3 4 5
6 7 8 9 10 11
1 2 3 4 5
6 7 8 9 10 11
1 2 3 4 5
6 7 8 9 10 11