Effective
10
/00
IL 33-K2C-3
Page 22
B.
For Kits Supplied with a PT Module Only:
Mount the PT Module to the Glass Poly Barrier,
as shown, using the (2) .138-32 × .500" screws,
(4) flat washers, (2) lock washers, and (2) nuts
supplied. Note that the PT Wires must be
routed towards the right side of the Aux. CT
Module.
Fig. 41 Correct Installation of the Support Clips
E. Secure the Trip Unit by tightening the 4.00"
screws installed in Step 8-C.
F.
Remove the Trip Unit Cover and install the
Rating Plug supplied with the Retrofit Kit.
Reinstall the Cover.
G. Install the Digitrip Nameplate on the top of the
Trip Unit.
Fig. 40 PT Module Mounted to the Glass Poly
Barrier
C. Mount the Trip Unit to the top of the Aux. CT
Module as shown using the (2) .190-32 × 4.00"
screws, (2) lock washers, (2) flat washers, and
(2) spacers supplied. Note that the spacers are
positioned between the top of the Aux. CT
Module and the bottom of the Trip Unit. Do not
tighten the screws at this time.
D. Mount the left and right Trip Unit Support Clips
to the sides of the Aux. CT Module and into the
bottom front slots in the Trip Unit as shown.
Secure the support clips using the (4) .190-32
× .375" screws, (4) flat washers, and (4) lock
washers supplied.
www
. ElectricalPartManuals