Effective
10
/00
IL 33-K2C-3
Page 30
Fig. 57 Connecting the DTA Harness
C. Connect the Sensor Harness to the proper
terminals of the 7-Point Terminal Block. Refer
to Section 12 of the Retrofit Application Data,
supplied with the Retrofit Kit, for detailed wiring
specifications.
Connect the green ground wire from the Sen-
sor Harness (with the ring terminal) to the rear
screw of the left Trip Unit Support Clip.
Fig. 58 Connecting the Sensor Harness
D. Route the Sensor Harness towards the left rear
of the Breaker, then through the hole drilled in
Step
3-A or B
.
Fig. 59 Routing of the Sensor Harness
E. Connect the ring terminals of the Sensor
Harness to the Sensors. Refer to Section 12 of
the Retrofit Application Data, supplied with the
Retrofit Kit, for detailed wiring specifications.
Depending on the Sensors supplied with the
Retrofit Kit, the following ratings apply.
Table 4
Sensor Taps Ratings
Sensor Style No.
Terminal Com.
Amps
8187A55H01:
X1-X2 =
200 A
8187A56H01:
X1-X4 =
800 A
X1-X3 =
600 A
X1-X2 =
400 A
8187A57H01:
X1-X4 =
1600 A
X1-X3 =
1200 A
8189A46H01:
X1-X2 =
2000 A
www
. ElectricalPartManuals
. com