Figure A.1 Typical Zone Interlocking
Figure A.2 Typical Zone Interlocking Connections with Two Main Breakers (M1, M2) and a Tie Breaker (T)
- B7 Contact
- B8 Contact
- B9 Contact
NOTES:
A1: Wiring to be twisted pair of AWG #14 to #20. Route Zone
Interlocking wiring separate from power conductors.
DO NOT GROUND (EARTH) any Zone Interlock Wiring.
A2: The maximum distance between two farthest breakers
on different zones (from the ZO downstream to ZI upstream
terminals) is 250 feet (76m).
A3: A maximum of 20 breakers may be connected in
parallel in one zone.
Is desired with other downstream breakers.
See Note A4